background image

 

M-2101-1: JBE-2101 Manual Call Point data sheet V1.0 

Jade Bird Fire Alarm Systems – JadeBird.eu.com                     2

  / 

Installation 

 

Always observe local fire and electric installation regulations. 

 

1.

 

Secure the base to the wall (surface or flush mounted). 

2.

 

Identify the system’s requirement for MCP alarm level (typically 680 Ω 

or 470 Ω). For other alarm loads, an external resistor may be used in 

conjunction with the internal voltage-free switch.  Note that the LED 

will not be powered from the voltage-free switch terminals. 

3.

 

Connect the conventional zone wiring to the MCP base.   

-

 

For 470 Ω zones, connect the wires as per diagram a). 

-

 

For 680 Ω zones, connect the wires as per diagram b). 

 

 

 

Terminals  Connection 

1 & 2 

Conventional zone (-) for 470 Ω zone 

3 & 4 

Conventional zone (-) for 680 Ω zone 

5 & 6 

[Optional] voltage-free switch (< 0.1A 30V DC) 

7 & 8 

Conventional zone (+) for all configurations 

 

 

4.

 

Insert the MCP face into its base and push firmly. 

5.

 

The head can be secured to the base by fitting an optional self-tapping 

screw (ST2.9x8) into its boss next to the reset keyhole. 

6.

 

Test each MCP and wiring integrity after installation. 

Reviews: