JADAC Power Support
3300 UPS Manual
Page 9 of 24
3.3
Transferring load to static bypass
Confirm:
“
No Active Alarms
” is displayed.
On Display Select:
3.4
Manual bypass (detour)
Perform
Load on Static Bypass
procedure.
Close Manual Bypass (CB3).
Open Load Output Isolator (SW1).
Open Rectifier Input (CB1).
Open Reserve Input (CB2).
Open Battery Fuses.
The unit will be safe to work on once the display has switched off.