JADAC Power Support
3300 UPS Manual
Page 5 of 24
2.0
INSTALLATION
2.1
Installation precautions
The following factors should be considered to determine a suitable location for your
unit:
•
Protection against excessive temperature and humidity
•
Protection against moisture
•
Ease of access and adequate lighting for service personnel
•
It’s position relative to the critical load for ease of reticulation
•
Adequate ventilation clearance (rear end)
•
A close proximity of the UPS to the battery cabinet where applicable
•
Potential expansion, e.g. additional battery cabinet/unit
2.2
General
The unit requires access from the front, top and from one side so care should be
taken in positioning the unit accordingly.
2.3
Cable and circuit breaker ratings
The recommended input, output cable and circuit breaker sizes are listed in the
table below. The input circuit breaker must have a
D curve
response and should
be mounted in the existing DB board. The UPS supply
must not
be connected via
an earth leakage breaker.
kVA
Rating
Input
Current
Circuit
Breaker
Input Cable
Output
Current
Output
Cable
10
32A
40A
10mm
2
15A
2.5mm
2
15
32A
40A
10mm
2
23A
4mm
2
20
32A
40A
10mm
2
30
6mm
2
30
63A
80A
16mm
2
45
10mm
2
40
63A
80A
25mm
2
60
16mm
2
All input and output cables should have four cores plus an earth respectively
2.4
Wiring layout and connections
The cable entry for the unit is at the rear behind a removable cover-plate.
Always ensure that all the cables are secure and the length adequate.
The terminal block layout and wiring numbering is shown on the next page.
It can bee seen that the reserve and rectifier terminals are bridged.
If it is required to supply the unit from two different sources, simply remove the
bridging cables.
The phase rotation must always be clockwise
.
The labeling notation is as follows:
Rectifier input terminals:
1U1, 1V1, 1W1 & 1N1
Reserve input terminals: 2U1, 2V1 & 2W1
Output terminals:
U2, V2, W2 & N2
The earth connection is made to the earth stud under the wiring compartment.