background image

10

JAUTP / JAUTPS CONTROLLER

SECTION 5.   

LOW VOLTAGE WIRING 

All low voltage wiring should be run through the 
knockouts in the low voltage compartment (right side 
of controller enclosure). See Figure 4.

 IMPORTANT 

Never run high voltage and low 

voltage in the same conduit.

(underside of controller enclosure)

low voltage  

knockout fittings

Figure 4. 

KNOCKOuTS  FOr  LOW VOLTAge WiriNg

5.1 

WIRE THE TEMPERATURE SENSORS

Wire the temperature sensors on the 10-pin green 
connector (see Figure 2. Wiring Diagram). The air 

temperature sensor is factory-installed on the 10-pin 

green connector (pins 7,8). The water temperature 
sensor and necessary installation hardware is included.

5.1.1 

INSTALL THE WATER  

TEMPERATURE SENSOR

1. 

Drill a hole for mounting the water temperature sensor 

line in the pipe between the pump and the filter (before 

the heater).

2. 

Install the O-ring on the sensor and insert the sensor 
into the hole. Wrap and tighten metal clamp around the 
pipe to secure sensor.

3. 

Feed the sensor wire through the black low voltage 
wiring knockout.

4. 

Strip 1/4” of insulation and separate the wires.

5. 

Connect sensor wires to pins 5 and 6 of the 10-pin 
green connector.

5.1.2 

INSTALL A SOLAR SENSOR  

(IF APPLICABLE)

If there is a solar panel in the equipment configuration, 
wire the solar panel temperature sensor to the 10-pin 

green connector. The solar sensor should be installed 
adjacent to the solar panel so it will sense the same 

temperature as the solar panels. Do not install in the 

pipe.

1. 

Feed the sensor wire through the black low voltage 
wiring knockout.

2. 

Strip 1/4” of insulation and separate the wires.

3. 

Connect sensor wires to pins 3 and 4.

5.1.3 

INSTALL ADDITIONAL  

LOW VOLTAGE EQUIPMENT  

(I.E., HEATER CONNECTION)

If there is additional low voltage equipment installed, 
such as low voltage heating, wire to pins 1 and 2 on the 

10-pin green connector (see Figure 2. Wiring Diagram).

5.2 

INSTALL IAQUALINK

®

  

JAUTPS/JAUTP (IF APPLICABLE)

NOTE:   

For complete intructions and safety  

 information, refer to the iAquaLink Quick Start 

Guide (included in the      iAquaLink packaging), 

or the full iAquaLink manual (found online at  

www. zodiacpoolsystems.com

).

5.2.1 

MOUNT THE IAQUALINK  

JAUTPS/JAUTP

 

DEVICE

Mount the iAquaLink JAUTPS/JAUTP at least 6 feet off 

the ground and at least 8 feet from motors, such as a 
blower. 

5.2.2 

WIRE THE IAQUALINK JAUTPS/JAUTP 

DEVICE

Wire the iAquaLink JAUTPS/JAUTP device on the red 

RS-485 connector (see Figure 2. Wiring Diagram).

1. 

Feed wire through the black low voltage wiring 
knockout.

2. 

Connect four (4) separate wires to each terminal 
(Figure 5).

Summary of Contents for JAUTPS

Page 1: ...arning notices and instructions that accompany this product Failure to follow warning notices and instructions may result in property damage personal injury or death Improper installation and or opera...

Page 2: ...s if applicable 11 Section 6 Section System Setup Programming and Testing 11 6 1 Basic Navigation 11 6 2 Set the Clock 12 6 3 Define Equipment ON OFF Schedules 12 6 4 Test the JAUTPS JAUTP 13 Section...

Page 3: ...adult Lower water temperatures are recommended for young children and when spa use exceeds 10 minutes b Since excessive water temperatures have a high potential for causing fetal damage during the ear...

Page 4: ...for complete details WARNING People with infectious diseases should not use a spa or hot tub To avoid injury exercise care when entering or exiting the spa or hot tub Do not use drugs or alcohol befor...

Page 5: ...ng Bracket for remotely installing UI Installation Manual Owner s Manual JAUTPS Four Function Controller with removeable User Interface UI Jandy Valve Actuators 2 Water Temperature Sensor Kit Mounting...

Page 6: ...ust be followed exactly Read through the Important Safety Information section completely before beginning installation and before operating the equipment Before you begin installation make sure you ha...

Page 7: ...Section 4 HIGHVOLTAGE WIRING WARNING Potentially high voltages in the JAUTPS JAUTP controller can create dangerous electrical hazards possibly causing death serious injury or property damage Turn off...

Page 8: ...VDC output JVA Sockets 24 VAC output Intake Return Solar Spare Input Low Voltage Heater Green Terminal Bar RS485 Network Red Terminal Bar User Interface Connector Black Modular Connector 24 VAC power...

Page 9: ...equipment requiring a ground should also be bonded to the common approved bonding point There should be one bonding connection to the controller In Canada the Canadian Electrical Code CEC dictates th...

Page 10: ...LAR SENSOR IF APPLICABLE If there is a solar panel in the equipment configuration wire the solar panel temperature sensor to the 10 pin green connector The solar sensor should be installed adjacent to...

Page 11: ...manual included in the JVA packaging 3 Install intake JVA and return JVA on equipment lines according to installation instructions in the owner s manual 4 Feed intake JVA wire through the black low vo...

Page 12: ...tes flash 5 Scroll up down to display desired minutes Press Select 6 3 DEFINE EQUIPMENT ON OFF SCHEDULES MAIN SETTINGS SCHEDULES Define automatic ON and OFF times for equipment You may set a total of...

Page 13: ...f Spa Pump On Pool Heat Off Spa heat Off Solar Heat Off More 12 40PM Pool Mode On Pool Heater 80 F Spa Mode Off Spa Heater Off Settings Devices Service Mode Devices Filter Pump Off Spa Pump On Pool He...

Page 14: ...me for about 5 seconds 12 40PM Pool Mode On Pool Heater 80 F Aux1 Off Aux2 Off Settings Devices INSTALL SETTINGS Freeze Protect Units Language Clear Memory Pump More INSTALL SETTINGS Color Light Label...

Page 15: ...ZE PROTECT EQUIPMENT Filter Pump Aux1 Aux2 Aux3 FREEZE PROTECT Set Temp Equipment FREEZE PROTECT EQUIPMENT Filter Pump Aux1 Aux2 Aux3 FREEZE PROTECT Set Temp Equipment 7 2 UNITS INSTALL SETTINGS UNITS...

Page 16: ...2 Speed VSP VSP Setup INSTALL SETTINGS Freeze Protect Units Language Clear Memory Pump More VSP SETUP Model Assign Speeds Prime Min Max Freeze VSP SETUP Model Assign Speeds Prime Min Max Freeze SET P...

Page 17: ...ty Assign JVA LABEL AUX Aux1 Aux2 Aux3 Label Aux2 Default Aerator Air Blower Backwash Chlorinator More Label Aux2 Swim Jet Valve s Wtr Feature Waterfalls Whirlpool More More INSTALL SETTINGS Color Lig...

Page 18: ...xiliary on the JAUTPS JAUTP controller so that when you select this auxiliary the valve turns Assigning JVAs lets the pool owner control certain features like diverting water to a waterfall or bank of...

Page 19: ...CES AQP 100 FFC 100 iAL 100 SWC 100 VSP 100 DIAGNOSTICS Revisions Alerts RS 485 Devices More INSTALL SETTINGS Diagnostics RS 485 DEVICES AQP 100 FFC 100 iAL 100 SWC 100 VSP 100 REVISIONS UI 1 3 Bootlo...

Page 20: ...es that all equipment is turned off until system is manually turned to Auto by service technician Timeout Indicates that all equipment will remain turned off for three 3 hours and then resume running...

Page 21: ...Heat Enabled Set to 102 F Boost OFF ON Low OFF ON Chlor Output Clock Schedules All Off Set Clock Friday 8 12 AM PM Filter Pump Spa Clner Sp3 Spillover Pool Heat Spa Heat Solar Heat AUX 1 AUX 2 AUX 3 o...

Page 22: ...t Negative Edge Not used Other 1 Other 2 Other 3 Pond Regulations Slide Solar Pump Spa Speed High Speed1 Speed2 Speed3 Speed4 Speed5 Speed6 Speed7 Speed8 Spillover Sprinkler 1 Sprinkler 2 Sprinkler 3...

Page 23: ...Clock Schedules All Off Set Clock Friday 8 12 AM PM Filter Pump Speed 2 Clner Sp3 Sp4 Temp 1 Temp 2 Solar Heat AUX 1 AUX 2 AUX 3 only shown if installed Pool 20 Spa Low 10 equipment name No Schedules...

Page 24: ...used Other 1 Other 2 Other 3 Pond Regulations Slide Solar Pump Spa Speed High Speed1 Speed2 Speed3 Speed4 Speed5 Speed6 Speed7 Speed8 Sprinkler 1 Sprinkler 2 Sprinkler 3 Vanishing Edge Swim Jet Valve...

Page 25: ...hen activated does not allow the function to work Section 11 GLOSSARIES 11 1 GLOSSARY OF SAFETY DELAYS AND LOCKOUTS Lockouts Any device can be locked out This will prevent the locked out device from b...

Page 26: ...PEN the heater will not fire If message AIR TEMP OPEN is displayed freeze protection will not operate correctly POOL HEATER ENABLED This message indicates that the pool heater is ready to use but is n...

Page 27: ...gh it preventing equipment damage TIMEOUT MODE TIME OUT mode is used by the pool service person to aid them in servicing the pool The JAUTPS JAUTP user interface will not be functional for three 3 hou...

Page 28: ...er brands product names company names trade names and trademarks used are the property of their respective owners Jacuzzi may add to change or remove any part of these materials at any time without no...

Reviews: