6. SEt3 – Service menu
The service parameters can be pre-programmed here. In normal mode it is not
necessary to change those parameters. The Service menu includes 8 items. Open
by scrolling the knob to the requested item and by pressing the knob to enter the
programming mode. Select the value again by scrolling the knob. Confirm it by
pressing the knob and it returns you back to the service menu.
HYst
is an item, where you can program the range of the
switching thresholds around the requested temperature
(hysteresis). The range can be set with a 0.1 °C step from
0.1 °C to 1 °C. (Default setting 0.2 °C)
Example:
With a set accuracy of 0.5
˚C a temperatu
re of 24
°C will be kept this way, at
23.5
°C it starts heating and at 24.
0
°C it stops heating. In real conditions regulation could
have a much bigger temperature scatter because of the thermal inertia in the heated
premises.
Warning: An over-narrow pre-programmed hysteresis range could perform
on/off switching of the heating very often.
The item
Stby
sets the temperature which will be kept in
the case of switching off the thermostat (item
OFF
).
The
Stby
temperature is always at least 3°C higher than
ALLo.
The value of the
Stby
temperature does not have to
be set higher than the
t Lo
temperature.
The
t Lo
item is the lower limit to which the economical
temperate can be set.
The
t Hi
item is the upper limit to which the comfort
temperature can be set.
AL Lo
is the lower critical temperature. When the
temperature drops under the pre-set value, the thermostat
sends an alarm report to the receiver and this state is
indicated by a permanently lit (
!
) symbol. The
ALLo
temperature is always at least 3 °C lower than
tLo
.
AL Hi
is the upper critical temperature. When the
temperature increases above the pre-set value, the
thermostat sends an alarm report to the receiver and this
state is indicated by a permanently lit (
!
) symbol. The
ALHi
temperature is always at least 3°C higher than
tHi.
For a reset to factory default settings the
RES
item is used
.
After you enter the menu and press the knob on the
RES
item
ON/OFF
appears. By scrolling the knob select
ON,
and press the knob. Then a RESET will be done.
When
the reset is finished, is need to set time, date and week
schedule.
By pressing the knob when the thermostat shows you
OK
you leave the service menu and return to the basic
thermostat menu.
Range of temperatures settings.
Settings
item
Range
Factory
settings
Description
HYst
0.1 °C to 1 °C
0.2 °C
Hysteresis
t Lo
+6 °C to +40 °C*
6 °C
Lower limit of
temperature
t Hi
+6 °C to +40 °C*
40 °C
Upper limit of
temperature
AL Lo
–9 °C to +20 °C
3 °C
Low temperature alarm
report
AL Hi
+30 °C to +70 °C
50 °C
High temperature alarm
report
Auto
On/OFF
On
Adaptive mode
+6 °C to +40 °C
19 °C
Economical temperature
+6 °C to +40 °C
22 °C
Comfort temperature
* The ranges of
t Lo
and
t Hi
can´t overlap each other.
Party mode
The thermostat can allow a special Party mode. In this mode the thermostat keeps
the temperature for a pre-defined time. You can only enter the party mode from the
weekly program (not from the manual mode). When that defined time expires the
thermostat goes back to the weekly program.
By turning the knob the ( ) symbol appears. Then by
pressing the knob enter the Party mode settings. The first
value is time (hrs) after which the thermostat returns to the
weekly program. Choose this value by turning the knob
and by pressing to confirm it. Then select the temperature which the thermostat will
keep by turning the knob, confirm by pressing. The Party mode is indicated by the ( )
symbol of a glass on the thermostat LCD display. The temperature can be pre-set in the
tLo
–
tHi
range
.
If you want to leave the party mode earlier than the pre-defined time, by turning the
knob select the weekly program and confirm by pressing.
Holiday mode
Because of saving costs when nobody is in the building, it is not necessary to keep
the pre-defined temperature in the service menu (a holiday typically) the thermostat
can be switched to the Holiday mode. The thermostat keeps the temperature pre-set
in the
Set1
menu. You can enter the holiday mode only
from the weekly program (not from the manual mode).
You can enter the Holiday mode only from the weekly
program (not from the manual mode) by turning the knob
until the suit case symbol appears. By pressing enter the
settings. The LCD display shows a flashing value of days for which the economical
temperature has to be kept. By turning the knob, pre-set the number of requested
days and then press the knob to confirm it. The time countdown starts from the
moment of setting. Subtraction is done every day at midnight. When Holiday mode
expires the thermostat returns to the weekly program. Note: The day when the
settings were done is also subtracted.
Showing the pre-set temperature
The thermostat always shows the current room temperature in the normal mode.
Briefly pressing the knob will show the temperature which has been set for this time.
The pre-set temperature flashes 3 s then it shows the current temperature again.
Replacing the batteries
When the thermostat starts to indicate the Low Batt symbol ( ) or stops working
completely, replace the batteries for new ones. A Low battery report is sent to the receiver.
Note:
We strongly recommend only using alkaline batteries, type AA 1.5 V.
Integration into the OASiS system
The thermostat can be
enrolled to a control panel as a detector
. If the temperature
decreases below
AL Lo
a
panic alarm
will be triggered = frost threat (heating failure).
If the temperature exceeds
AL Hi
then a
fire alarm
will be triggered.
An AC-82 receiving unit (AC-82) has two output relays (X and Y). Thermostats can be
enrolled separately to each relay in order to
control two independent heating circuits
.
To operate a heating system the OASIS control panel
can also be enrolled (sequence
299) to the same relay of the receiving unit (AC-82) as the thermostat is enrolled to. A
thermostat enrolled to the
X
relay
can be operated via the PGX programmable output
,
and a thermostat enrolled to the
Y
relay operated via
PGY
. If the programmable
output of
the control panel is switched on,
the thermostat maintains the programmed temperature.
If the control panel´s output is
switched off
the thermostat only triggers heating if the
temperature drops
below
Stby.
To operate the heating, RC-80 or RC-88 remote controls can also be enrolled to receiving
unit (AC-82). The heating can be switched on by remote controls to heat the desired
temperature and also
switched off where it only heats when the temperature is below
Stby
.
To disable heating when windows are open
JA-81M or JA-82M
detectors
can also be
enrolled to the same relay as the thermostat is enrolled to. If the windows are closed it
heats
to the desired temperature and if windows are open it
heats only when the temperature is
below
Stby
.
Up to 8 thermostats
can be enrolled to a single relay. If at least on the thermostat
transmits a heat command then the relay will be switched on.
Technical specifications
Power:
2x AA LR6 1.5 V / 2.4 Ah
alkaline batteries
Lifetime of batteries:
typically
2years
Regulation range:
+6
°C to +40
°C
Temperature regulation sensitivity:
adjustable: 0.1
- 1
°C
Alarm when temperature drops below ALLo:
-9
°C to +20
°C
Alarm when temperature exceeds ALHi:
+30
°C to +70
°C
Communication band:
868.5 MHz, O
asis
protocol
RF r
ange:
up to 100 m (open area)
Operational temperature:
-10
°C to + 70
°C (no condensation)
Dimensions:
66 x 90 x 22 mm
Complies with
ETSI EN 300220, EN
50130-
4,
EN
55022, EN 60950
-1
Can be operated according to
ERC REC 70
-03
JABLOTRON ALARMS a.s. hereby declares that the TP-83N module is in compliance
with the essential requirements and other relevant provisions of Directive 1999/5/EC
and 2011/65/EU. The original of the conformity assessment can be found at
- Technical Support section
Note:
Although this product does not contain any harmful materials we suggest you
return the product to the dealer or directly to the producer after use. For more detailed
information visit