jablotron OASiS JA-82KRC Installation Manual Download Page 6

Installation manual: OASiS security system JA-82KRC   

6 / 21 

MKH51100_OS2

 

When equipped with a JA-82R module, the control panel also 

allows for a JA-80F wireless keypad connection. 

 

Modular connection

cable

Control and programming

keypad JA-80E

 

We recommend only having a single JA-80E hard-wired 

keypad in the system. 

6. Back-up 

battery 

It is possible to use a Jablotron-brand 12V back-up battery in 

the control panel with a capacity of 2.2 Ah. The capacity to use 
depends on the total power consumption of the system and the 
desired back-up period.  

 Euro-standard EN 50131-1 specifies a 12 hour minimum 

back-up time for grade 2 systems. The standby consumption of 
all system devices is shown in 

Table 1

 

 With 

2.2Ah

 back-up battery 12 hours of back-up time can 

be realised if current consumption does not exceed 

150mA

This only takes 80% of the battery capacity into account as 
20% has to be reserved for battery aging effects. 

 The average

 back-up battery lifetime 

is

 up to 5 years 

after which it must be replaced. The back-up battery is 
automatically charged and its condition is monitored by the 
system. If the system is being run on only the back-up 
battery a technical alarm occurs when the battery is nearly 
discharged. If the voltage gets too low the battery will be 
disconnected. After the mains supply has been restored 
battery charging starts again and the system will begin to 
function again. 

Table 1-  standby consumption of system devices

  

 

 

Ensure that the battery is correctly connected (Polarity: RED = 
po, BLACK = negative -).

 

WARNING – the battery is sold charged – to maintain safety, 
avoid shorting out the terminals !!! 

 

7.  Powering-up the control panel for the 

first time 

  First check all the wiring, and if a GSM communicator is 

installed, insert its SIM card (PIN code disabled).  

 Carefully 

connect 

the back-up battery, 

  Carefully connect up the mains. A green LED will start 

flashing on the control panel board. 

  If a hard-wired keyboard is connected it will indicate Service 

mode. If not, the control panel is not set to the factory default 
and should be reset (see section

 9.

). 

7.1. 

Wireless keypad enrollment 

If no hard-wired keypad is connected to the control panel, 

and the wireless keypad was not supplied as part of a JK kit, 
the  wireless keypad must be enrolled to the control panel as 
follows:   

1.  Have an opened keypad and its battery ready. 
2.  Check that the green LED in the control panel is flashing.  
3. Short the reset link in the control panel for 1 second (e.g. 

using a screwdriver). This will enter enrollment mode on the 
control panel. 

4. Install batteries into the keypad not far from the control 

panel. 

5.  The keypad generates a beep sound and enrolls to address 

05 (or 15). After that it indicates “Enrollment 06: Device” (or 
“Enrollment 16: Device”). 

6. Press  the 

key to exit enrollment mode and “Service” will 

be indicated on the keypad. 

Warning: 

  If the keypad does not enroll, then the control panel settings 

are not the factory-defaults. In this case perform a reset and 
repeat the enrollment procedure. 

  If you want to assign the keypad to another address, re-

enter enrollment mode  via the “1” key, then use the arrow 
keys to select the desired address. Then disconnect the 
keypad battery and reconnect it. 

Recommendation: it is highly recommended to install the 
wireless keypad with a magnetic door sensor wired to its hard-
wired input terminal. This way the keypad will wake up every 
time after opening the door and it will produce entrance delay 
beeps and will be ready to read access cards. It will also save 
money on a wireless door detector.  

8.  Language selection of the keypad 

If the 

∗ 

 key is kept pressed during battery connection, the 

internal keypad menu will be displayed allowing the selection 
of the 

desired language

. Using the arrows, choose your 

language and confirm selection by the 

∗ 

 key. 

In this menu the 

door bell function

 can also be enabled or 

disabled (if enabled the keypad makes a sound when its IN 
input is triggered). 

Notes: 

  for the JA-80E wired keypad the power can be connected 

by connecting its cable or by turning on the control panel 
power  

 if the wireless keypad has already had its battery 

connected, it is necessary to disconnect the battery for a 
while before pressing and holding the 

 key 

  the language can be selected for each individual  keypad in 

the system (i.e. different keypads can display different 
languages – for example if foreigners are working in the 
company) 

9.  Resetting the control panel 

If you need to return the control panel to the factory-default 

settings perform the following:   

1.  Disconnect the back-up battery and the mains (for example 

by removing the fuse from its terminals). 

2. 

Connect the RESET

 link and leave it connected. 

3.  Connect the back-up battery and the mains. 
4. Wait till the green 

LED

 starts flashing and then disconnect 

the 

RESET

 link. 

Device mA 

Note 

Control panel JA-82K 

10 

No communicator 

Module JA-82R 

20 

 

Module JA-82C 

15 

 

Keypad JA-80E 

30 

 

Keypad JA-80H (N) 

60 

Including a WJ-80 interface  

Communicator JA-80Y 

35 

 

Communicator JA-80V 

30 

 

Communicator JA-80X 

15 

 

Wireless devices are not powered from the control panel. 

Summary of Contents for OASiS JA-82KRC

Page 1: ...nual OASiS security system JA 82KRC 1 21 MKH51100_OS2 JA 82KRC OASiS Control panel installation manual This manual is valid for control panel JA 82KRC The control panel can be configured by a PC running OLink software ...

Page 2: ...dible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Automatic summer time daylight saving time 14 12 26 Tamper alarm in response to an increase in the number of triggered tamper sensors 14 12 27 Operating the PG outputs using 8 and 9 14 12 28 Permanent ...

Page 3: ...e control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disables the wireless input of the same address o Other hard wired inputs are provided by some wireless devices such as keypads door detectors and PIR movement detectors 1 1 Main features When triggered a detector or any other device conn...

Page 4: ...or Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The control panel must have one of the following configurations as a minimum At least two non backup battery sirens JA 80L or SA 105 communicator class ATS2 JA 80Y JA 80V or JA 80X At least one backup bat...

Page 5: ... parallel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETECTOR 2 DETECTOR 3 Maximum of 5 detectors in one loop If you enroll a wireless device to address 01 to 04 the corresponding input terminal will be disabled o The same applies to input terminals 05 ...

Page 6: ...e control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a beep sound and enrolls to address 05 or 15 After that it indicates Enrollment 06 Device or Enrollment 16 Device 6 Press the key to exit enrollment mode and Service will be indicated on the keypad Warnin...

Page 7: ...onnection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery Then wait about 10 seconds or to save time press and release its tamper switch to quickly discharge any remaining energy A sub control panel can be enrolled to a master control panel by keying in the...

Page 8: ...ne multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be programmed by keying in the sequences in section 12 1 The system should be in Service mode if not enter the following with the system unset 0 Service code the factory default is 8080 Enter the appropriate...

Page 9: ...ng Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES NO siren only sounds if the system is completely set armed Wireless siren alarms enabled IW EW 38x 381 YES 380 NO YES Auto bypass user approval via the key If a detector is active during setting armin...

Page 10: ...as the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card reactions and section assignment A code card may have the same kind of reaction as devices 62 nn r s nn address 01 to 50 r reaction 0 disabled incl tamper sensor 1 Natural this means for detectors select...

Page 11: ...y alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the keypad by keying in 8 9 or using the arrow keys see 12 27 or they can be operated by a code or card These PG output functions can also controlled by signals from keyfobs or detectors see 12 41 Notes T...

Page 12: ...aster code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12 Control panel enrollment to UC or AC modules or to a sub control panel Keying in 299 sends an enrollment signal to enroll the control panel to UC 82 or AC 82 receiving modules see 11 6 This sequence...

Page 13: ...21 Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no effect on wired output terminals Factory default setting wireless sirens enabled 12 22 Auto bypass user approval via the key The system has a built in auto bypass function so that if any number of de...

Page 14: ...unset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially suitable for homes and apartments where the user wishes to protect different parts of the premises during the day Detectors can be assigned to three sections A B and C Using setting arming key A on the...

Page 15: ...her or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 6900 notification disabled 6901 notification enabled Notes An annual technical inspection notification is displayed as text on the keypad display and can also be sent as an SMS to the end user and or i...

Page 16: ...e hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or system splitting is used except for PG output control Guidance on assignment to sections Assigning keyfobs with natural reactions to sections s button Unsplit system Partial setting Split system or set s...

Page 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory default setting all codes cards from 01 to 50 have a natural reaction set unset and are assigned to section C 12 42 Enrollment by keying in production codes This sequence allow the enrollment of device...

Page 18: ...ext is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypads also use so called internal text such as service maintenance mode etc and this text can also be edited via OLink software by selecting Settings on the menu and then keypad text After editing keyp...

Page 19: ... codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same code or card to be programmed to multiple users if it is desired to move a code card to another user the card code has to be e...

Page 20: ...0 can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press the key 5 To exit maintenance mode press the key To change access codes and cards use sequence 6 MC nn NC see 13 2 The most convenient way to administer codes is by using a PC running OLink software 13...

Page 21: ...control panel The wireless keypad does not indicate entrance delays by beeping If the keypad is only battery powered then it turns off 20 seconds after the last time a key was pressed To indicate entrance delays first wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Altern...

Reviews: