jablotron OASiS JA-82KRC Installation Manual Download Page 10

Installation manual: OASiS security system JA-82KRC   

10 / 21 

MKH51100_OS2

 

Engineer reset 

668x 

6851 = YES     6850 = N0

 

NO

 

 

Annual check requirement display 

If enabled then 12 months after exiting Service Mode an 
annual technical check request is displayed on the keypad unit 
(mobile phone & ARC notification optional)

 

690x 

6901 = YES     6900 = NO 

NO 

 

Only single alarm indication 

If enabled then another intruder alarm can not be triggered 
during an intruder alarm currently in progress.

 

691x 

6911 = YES     6910 = NO 

NO 

 

Setting (arming) by service code 

692x 

6921 = YES     6920 = NO 

NO 

only with the master 
code holder’s  
approval  

Audible panic alarm 

693x 

6931 = YES     6930 = NO 

NO  

Higher control-panel receiver-sensitivity 

Extends the communication range if there is no RF 
interference 

 

694x 

6940 = normal    6941 = higher 

normal  

Access by Code plus

 

Card

  

If enabled and there is a code and card assigned to the same 
user, then both of them must be presented for setting (arming) 
control (in any order).

 

695x 

6951 = Code+Card     

 6950 = Code or Card 

code or 

card 

 

Audible 24h intruder alarm

 

696x 

6961 = YES     6960 = NO 

YES  

Service mode only with S Master code 

697x 

6971 = YES     6970 = NO 

NO  

Device reactions and section assignment 

(detectors, 

key fobs, control panel and keypad inputs) 

 

A detector’s natural reaction

 can be INS, DEL or Fire 

(selectable in the detector) 

 

The natural reaction

 of 

Control panel & Keypad wired 

inputs  

is DEL 

Keyfob natural reactions: 

 (or

)= SET (arm) , 

 

(or

)= UNSET (disarm) and both simultaneously = Panic. If a 

reaction from 2 to 8 is selected (see opposite), only the key 

 (or

) and double buttons 

 + 

 (

+  ) will have it. 

The 

  (

) button has no effect (can still be used for 

controlling UC/AC receivers).

 

 

Assignment to sections

 will only have an effect on partial 

arming or if the system is split (except PG output control)   

 

For partial arming, 

a

 

pair of 

keyfob

 buttons assigned to 

section: 

A has the effect:

 

 (or

)=SET A, 

 (or

)=SET AB  

B has the effect:

 

 (or

)=SET A, 

 (or

)=SET AB 

C has the effect:

 

 (or

)=SET ABC, 

 (or

)=UNSET 

ABC

 

 

In a split system, a keyfob

 button pair assigned to section: 

A=SET/UNSET A, B =SET/UNSET B, C =SET/UNSET ABC 

 

61 nn r s 

Code (card) reactions and section assignment 

 A code (card) may have the same kind of reaction as 

devices 

62 nn r s 

 
nn 

address

 01 to 50  

r = reaction

 

 0 disabled (incl. tamper sensor) 
 1 

Natural 

– this means: 

for detectors

=selected by 

DIP switch in the detector,  

for wired inputs

=DELay, 

for Codes 
(cards

)=SET/UNSET 

 2 Panic 
 3 Fire 
 4 24 hours 
 5 Next DELay 
 6 INStant 
 7 SET (arm) 
 8 PG control (s: 1=PGX,         
2=PGY,3=PGX+PGY) 
 9 SET/UNSET (toggle) 

 

 

 

s = section

 1=A, 2=B, 3=C - has 

to be entered even if the system 
is not split and setting 
(arming)has no meaning.  
In a split system, a code (card) 
assigned to C will SET/UNSET 
all ABC sections 

 

 
 
 
 
 
 
 
 

all Natural 

in C 

 
 
 

 
 
 

Enrollment by keying in production codes 

 60 nn xxxxxxxx 

nn

 = address 01 to 50, 

xxxxxxxx

 = last 8 digits of the 

production code (below the bar code on the device)  

Automatic Daily Setting/Unsetting schedule 
(arming/disarming) 

64

nahhmm

 

n –

 action sequence index (0 to 

9)  

a –

 action: 

 0=no action 
 1=SET ABC 
 2=UNSET ABC 
 3=SET A 
 4=SET B (if unsplit then AB) 
 5=UNSET A (if unsplit then ABC) 
 6=UNSET B (if unsplit then ABC) 

hh -

 hours, 

mm - 

minutes 

 

No action 

 

The scheduled 
actions will happen 
every day 

Changing the service code 

5 NC NC 

NC = new code

 (4 digits)  

8080 

enter NC twice  

Go to maintenance mode 

292 

switches to 

maintenance

 

mode 

-  

Setting the internal clock 

4 hh mm DD MM YY

 

00:00 1.1.00   

Editing keypad text 

Text for device names, code names and PG output names 
are stored in each individual keypad.  
 

Press and hold the 

?

 key to enter text editing 

(the first character of the first address name 
will start flashing). Then use keys: 

 and 

 to select some text (or an address)  

1

 & 

7

  character selection (A,B,C,D...8,9,0) 

4

 & 

5

 cursor (to the left & right) 

2

 to erase a character 

# = 

exit editing

 and save changes 

 
Device 

Only capital letters 
can be entered this 
way. If there are 
multiple keypads, 
each must be edited 
individually this way 
or all of them can be 
easily  programmed 
via OLink software 

 

Summary of Contents for OASiS JA-82KRC

Page 1: ...nual OASiS security system JA 82KRC 1 21 MKH51100_OS2 JA 82KRC OASiS Control panel installation manual This manual is valid for control panel JA 82KRC The control panel can be configured by a PC running OLink software ...

Page 2: ...dible alarms 13 12 21 Wireless siren alarm enabled IW and EW 13 12 22 Auto bypass user approval via the key 13 12 23 Final door detectors 13 12 24 Partial setting arming or system splitting 14 12 25 Automatic summer time daylight saving time 14 12 26 Tamper alarm in response to an increase in the number of triggered tamper sensors 14 12 27 Operating the PG outputs using 8 and 9 14 12 28 Permanent ...

Page 3: ...e control panel does not allow for the simultaneous connection of both a wired and a wireless input to the same address Connecting to a wired input automatically disables the wireless input of the same address o Other hard wired inputs are provided by some wireless devices such as keypads door detectors and PIR movement detectors 1 1 Main features When triggered a detector or any other device conn...

Page 4: ...or Maintenance modes 1 2 Optional system configurations In the European Union region follow the valid standards and rules especially series EN 501 xx The Oasis control panel complies with grade 2 The control panel must have one of the following configurations as a minimum At least two non backup battery sirens JA 80L or SA 105 communicator class ATS2 JA 80Y JA 80V or JA 80X At least one backup bat...

Page 5: ... parallel resistors see the diagram below o For wiring examples see the below diagram TAMPER SIREN ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION TAMPER ACTIVATION ACTIVATION DOOR 1 DOOR 2 DETECTOR 1 DETECTOR 2 DETECTOR 3 Maximum of 5 detectors in one loop If you enroll a wireless device to address 01 to 04 the corresponding input terminal will be disabled o The same applies to input terminals 05 ...

Page 6: ...e control panel for 1 second e g using a screwdriver This will enter enrollment mode on the control panel 4 Install batteries into the keypad not far from the control panel 5 The keypad generates a beep sound and enrolls to address 05 or 15 After that it indicates Enrollment 06 Device or Enrollment 16 Device 6 Press the key to exit enrollment mode and Service will be indicated on the keypad Warnin...

Page 7: ...onnection to the control panel possibly due to excessive distance or it could be too close to the control panel closer than 2 meters is not permitted To re enroll a device first disconnect its battery Then wait about 10 seconds or to save time press and release its tamper switch to quickly discharge any remaining energy A sub control panel can be enrolled to a master control panel by keying in the...

Page 8: ...ne multiple control panels in one UC or AC receiver 12 Control panel programming The most convenient way to program the system is to use a PC running OLink software The system can however also be programmed by keying in the sequences in section 12 1 The system should be in Service mode if not enter the following with the system unset 0 Service code the factory default is 8080 Enter the appropriate...

Page 9: ...ng Entrance delay beeps 35x 351 YES 350 NO YES Setting arming confirmation by wired siren chirp 36x 361 YES 360 NO NO IW terminal only Siren always sounds during audible alarms 37x 371 YES 370 NO YES NO siren only sounds if the system is completely set armed Wireless siren alarms enabled IW EW 38x 381 YES 380 NO YES Auto bypass user approval via the key If a detector is active during setting armin...

Page 10: ...as the effect or SET A or SET AB C has the effect or SET ABC or UNSET ABC In a split system a keyfob button pair assigned to section A SET UNSET A B SET UNSET B C SET UNSET ABC 61 nn r s Code card reactions and section assignment A code card may have the same kind of reaction as devices 62 nn r s nn address 01 to 50 r reaction 0 disabled incl tamper sensor 1 Natural this means for detectors select...

Page 11: ...y alarm PG on excluding Panic Panic A PGX on Panic B PGY on 6 AC dropout PG on Fire PGX on dropout PGY on 7 ON OFF 8 2 seconds pulse The ON OFF and 2 second pulse functions can be controlled from the keypad by keying in 8 9 or using the arrow keys see 12 27 or they can be operated by a code or card These PG output functions can also controlled by signals from keyfobs or detectors see 12 41 Notes T...

Page 12: ...aster code has no effect on other codes and cards Resets are recorded in the control panel memory and sent to the ARC if used Alarm Receiving Centre previously called a central monitoring station 12 12 Control panel enrollment to UC or AC modules or to a sub control panel Keying in 299 sends an enrollment signal to enroll the control panel to UC 82 or AC 82 receiving modules see 11 6 This sequence...

Page 13: ...21 Wireless siren alarm enabled IW and EW This setting is for enabling and disabling wireless sirens in the system 3 8 1 wireless sirens enabled 3 8 0 wireless sirens disabled Note This setting has no effect on wired output terminals Factory default setting wireless sirens enabled 12 22 Auto bypass user approval via the key The system has a built in auto bypass function so that if any number of de...

Page 14: ...unset immediately after the user sets unsets the system Assigning wireless devices access codes and keyfobs to various sections of the system has no effect in this mode Partial setting is especially suitable for homes and apartments where the user wishes to protect different parts of the premises during the day Detectors can be assigned to three sections A B and C Using setting arming key A on the...

Page 15: ...her or a JA 80V version XA64005 or higher is installed 12 32 Annual check notification This sequence enables the user and installer to be notified of the necessary time for an annual technical check 6900 notification disabled 6901 notification enabled Notes An annual technical inspection notification is displayed as text on the keypad display and can also be sent as an SMS to the end user and or i...

Page 16: ...e hard wired input terminals in the control panel or enrolled wireless devices r is the reaction index from 0 to 9 see Table 2 s is the section 1 A 2 B 3 C only has an effect if partial setting or system splitting is used except for PG output control Guidance on assignment to sections Assigning keyfobs with natural reactions to sections s button Unsplit system Partial setting Split system or set s...

Page 17: ...rd has a natural reaction i e r 1 then its reaction is set unset set etc the same as reaction r 9 in table 2 A code card can also have an alarm reaction designated to it similar to detectors Factory default setting all codes cards from 01 to 50 have a natural reaction set unset and are assigned to section C 12 42 Enrollment by keying in production codes This sequence allow the enrollment of device...

Page 18: ...ext is stored in the non volatile memory of keypads so power disconnection will not erase any stored text Convenient text editing is possible using a PC running OLink software Besides device names keypads also use so called internal text such as service maintenance mode etc and this text can also be edited via OLink software by selecting Settings on the menu and then keypad text After editing keyp...

Page 19: ... codes and cards from 01 to 50 are erased If a user has both a code and a card then it is possible to program whether both a code and card must be presented to the system for system access or whether only one of them is required see 12 37 The system does not allow the same code or card to be programmed to multiple users if it is desired to move a code card to another user the card code has to be e...

Page 20: ...0 can be scrolled through with the A indicator showing whether a code is programmed or not and the B indicator showing whether a card is programmed or not 4 To exit this code card display mode press the key 5 To exit maintenance mode press the key To change access codes and cards use sequence 6 MC nn NC see 13 2 The most convenient way to administer codes is by using a PC running OLink software 13...

Page 21: ...control panel The wireless keypad does not indicate entrance delays by beeping If the keypad is only battery powered then it turns off 20 seconds after the last time a key was pressed To indicate entrance delays first wake it up Install an ordinary magnetic sensor to the entrance door wiring it to the keypad input so that opening the door wakes up the keypad and reports to the control panel Altern...

Reviews: