The JA-82ST wireless combined smoke and heat detector 

 

MZZ57307 

 

The JA-82ST wireless combined smoke and heat detector  

The JA-82ST is a wireless component of the JABLOTRON ALARMS 

OASIS alarm system. It is used to detect fire hazards in the interior of 

residential or commercial buildings. It is not designed to be installed 

outdoor or in industrial premises. The detector is powered by three LR6 

(AA) type alkaline batteries, which are not included. We recommend you buy 

them together with the detector. The JA-82ST consists of two independent 

detectors  –  an optical smoke detector and a heat detector. The optical 

smoke detector works on the principle detection of scattered light and is 

very sensitive to large dust particles which are present in dense smoke.  

It is less sensitive to smaller particles generated by the combustion of 

liquids such as alcohol. That is why there is also a built-in heat detector 

which has a slower reaction but is much better at detecting fire which 

generates heat with a small amount of smoke. The detector has a status 

reaction (reports its activation and deactivation). The detector should be 

installed by a trained technician with a valid certificate issued by an authorized 

distributor. 

Detector range and location 

The smoke detector must be installed so that any smoke easily drifts 

into the detector owing to natural thermal circulation, e.g. on the ceiling. It is 

suitable for residential buildings but not suitable for free spaces, outdoor 

environments or interiors with extremely high ceilings (above 5 m) where 

fire by-products can disperse over a large area –  the smoke would not 

reach the detector position. 

The detector must always be placed in the section leading to the exit 

of the building (escape route), see Figure 1. If the building has a floor 

area greater than 150 m2, installation of an additional detector in some 

other suitable place is required, see Fig.2.  

 

1

2

3

4

5

 

 

1. kitchen,  
2. living room,  
3. – 6. bedrooms  

 

 / 

     

basic coverage 

 

 

recommended 

coverage 
 

Fig 1 

1

2

3

4

5

6

 

Fig 2 

1

2

3

6

 

Fig 3 

 

In buildings and family houses with multiple floors, detectors should be 

installed above stairwells. It is recommended to place additional detectors in 

rooms where people sleep. See fig 3.

 

Installation on level ceilings 

Place the detector in the center of the room if possible. The detector 

must not be recessed into the ceiling due to the possible existence of a 

cool air layer on the ceiling. 

Never place the detector in the corner of 

the room though

 (always keep at least a 0.5 m distance from the corner) 

see Fig 4. There is an insufficient circulation of air in the corners. 

Installation on sloping ceilings 

If the ceiling is not suitable for mounting on a level surface (e.g. a 

room under a roof ridge), the detector can be installed as in Fig. 5 

0.5m

TOP

 

Fig 1 

 

0,9 m

 

 

Fig 2 

 center of the room, best location  

acceptable location 

Walls, partitions, barriers and lattice ceilings 

The JA-82ST detector must not be installed closer than 0.5 m 

from any wall or partition. 

A narrow space with a width of less than 1.2 

m requires the detector to be placed at a distance of at least one third of 

its width away. If a room is separated into sections with furniture, racks or 

semi partition walls, which do not reach the ceiling, 

the  space is 

considered to be fully separated if the gap between the top of the 

separating wall and the ceiling does not exceed 0.3 m.

 A free space 

of at least 0.5 m is required under and around the detector. Any 

irregularities of the ceiling (e.g. girders) exceeding 5 % of the ceiling 

height shall be considered a wall and the above mentioned limitations 

shall apply.  

Ventilation and air circulation 

The detectors must not be installed directly by ventilation or air 

conditioning vents, etc… 

If the air is supplied through a perforated ceiling, 

there must be no perforation within a radius of 0.6 m of the detector. 

Avoid installing the detector in the following locations:

 

  Places with poor air circulation (niches, corners, apexes of  

A-shaped roofs, etc.) 

  Places exposed to dust, cigarette smoke or steam 

  Places with over-intense air circulation (close to ventilators, heat 

sources, air conditioning outlets, etc.) 

  In kitchens and other cooking places (because steam, smoke or oily 

fumes can reduce detector sensitivity, thus cause false alarms and 

detection faults). 

  Within a 1 m radius of fluorescent tubes or energy-saving light bulbs 

(electrical interference may negatively affect the detector’s radio 

communication) 

  In areas with lots of small insects 

 

Please note: The most false alarms are caused by  

improper detector location.

 

See  CEN/TS 54-14 standard for detailed installation guidelines.

 

Installation 

Abide by the procedures recommended in the previous paragraphs.  

 

 

Fig 3: 1– detector cover opening; 2 – detector cover closing; 3 – optical status 

signaling; 4 – arrow showing where to insert the detector; 5 – enrollment code;  

6 – configuration terminals; 7 – battery holders    

 

1. 

Open the detector cover, by turning it anti-clockwise (1)

 

2. 

Attach the removed plastic base

 to the desired place with screws  

3. 

Set the configuration terminals (6) according to the table below.

 

4.  Proceed according to the control panel installation manual. Basic 

procedure: 

a.  Switch the control panel to the Service mode and enter the 

enrollment mode by pressing 1.  

b.  When you insert all batteries into the detector, the enrollment code 

is sent to the system – its sending is confirmed with a short flash of 

the LED indicator (3). 