background image

The JA-80S wireless fire detector 

 

MHS51505 

the  fire  reaction  is  set).  The  strength  and  quality  of  detector  signals  can  be 
measured by the control panel in Service mode. During testing by the test button, 
the  detector  transmits  signals  which  can  not  trigger  fire  alarms  in  the  control 
panel.  

Warning: Never start a fire in a building to test the detector

.  Instead, use 

smoke-simulating aerosols for realistic testing. 

 

Silencing the siren during an alarm 

During a fire alarm, the detector LED flashes 2 times briefly and the built-in siren sounds 

(at a higher intensity than during a test). Under these conditions the siren can be silenced by 
pressing  the  test  button  for  approx.  3  sec.  The  LED  will  continue  to  flash  until  the 
smoke clears from the room (indication is valid only for FIRE settings).  

However, if normal conditions are not restored within approx. 10 minutes (the smoke does 

not clear from the room or the temperature does not drop), the siren re-activates.   

 

Fault indication 

The detector performs regular self-testing. If a fault is detected in the detector, 

its LED will start to flash rapidly. In such a case, disconnect the battery from the 
detector,  and  after  about  20  secs,  re-connect  it.  If  after  a  minute  the  LED  still 
flashes, then send the detector off for repair. 

 

Battery replacement 

The detector monitors its battery voltage and if too low, a transmission is sent to 

the control panel to inform the installer or  user. The detector continues to function 
but with a short LED flash every minute. Battery replacement should not be delayed 
by  more  than  two  weeks.  This  should  be  done  by  a  qualified  technician  with  the 
control panel in Service mode. 

After battery replacement, test the functioning of the detector using its test button. 

Expired batteries should not be thrown into the garbage, but disposed of according 
to local regulations.  

 

Removing the detector from the system 

If a detector is removed, the control panel announces the removal. The detector 

has to be deleted in the control panel before intentional removal. 

 

 

Technical parameters 

Voltage: 

Lithium battery type or LST14500 (AA 3.6V / 2,4 Ah) 

Typical battery lifetime 

approx. 3 years 

Communication band 

868,5 MHz, Oasis protocol 

Smoke detection 

optical, scattered light 

Smoke sensor sensitivity 

 m = 0.11 - 0.13 dB/m to EN 54-7

 

Temperature detection 

class A2 to EN 54-5 

Fire-alarm temperature 

+60 °C to + 70 °C 

Acoustic power of the built-in siren 

80 dB/m   

Operational temperature range 

-10

°C to +80 °C 

Dimensions, weight  

diameter: 126 mm, height: 65 mm, 200 g 

Complies with  

EN 54-7, EN 54-5 class A2, EN 54-25,  

 

ETSI EN 300220, EN 50130-4, EN 55022, EN 60950-1 

Can be operated according to 

ERC REC 70-03 

 

 

1293-CPD-0263 

 

JABLOTRON ALARMS a.s. hereby declares that the JA-80S

 

is in compliance 

with  the  essential  requirements  and  other  relevant  provisions  of  Directives 
1999/5/EC and 1989/106/EC. The original of the conformity assessment can be 
found a

www.jablotron.com

Technical support section. 

 

 Note:

  Although  this  product  does  not  contain  any  harmful 

materials we suggest you return the product to the dealer or directly 
to the producer after use. 

 
 

 