The JA-80S wireless fire detector
MHS51505
2
the fire reaction is set). The strength and quality of detector signals can be
measured by the control panel in Service mode. During testing by the test button,
the detector transmits signals which can not trigger fire alarms in the control
panel.
Warning: Never start a fire in a building to test the detector
. Instead, use
smoke-simulating aerosols for realistic testing.
Silencing the siren during an alarm
During a fire alarm, the detector LED flashes 2 times briefly and the built-in siren sounds
(at a higher intensity than during a test). Under these conditions the siren can be silenced by
pressing the test button for approx. 3 sec. The LED will continue to flash until the
smoke clears from the room (indication is valid only for FIRE settings).
However, if normal conditions are not restored within approx. 10 minutes (the smoke does
not clear from the room or the temperature does not drop), the siren re-activates.
Fault indication
The detector performs regular self-testing. If a fault is detected in the detector,
its LED will start to flash rapidly. In such a case, disconnect the battery from the
detector, and after about 20 secs, re-connect it. If after a minute the LED still
flashes, then send the detector off for repair.
Battery replacement
The detector monitors its battery voltage and if too low, a transmission is sent to
the control panel to inform the installer or user. The detector continues to function
but with a short LED flash every minute. Battery replacement should not be delayed
by more than two weeks. This should be done by a qualified technician with the
control panel in Service mode.
After battery replacement, test the functioning of the detector using its test button.
Expired batteries should not be thrown into the garbage, but disposed of according
to local regulations.
Removing the detector from the system
If a detector is removed, the control panel announces the removal. The detector
has to be deleted in the control panel before intentional removal.
Technical parameters
Voltage:
Lithium battery type or LST14500 (AA 3.6V / 2,4 Ah)
Typical battery lifetime
approx. 3 years
Communication band
868,5 MHz, Oasis protocol
Smoke detection
optical, scattered light
Smoke sensor sensitivity
m = 0.11 - 0.13 dB/m to EN 54-7
Temperature detection
class A2 to EN 54-5
Fire-alarm temperature
+60 °C to + 70 °C
Acoustic power of the built-in siren
80 dB/m
Operational temperature range
-10
°C to +80 °C
Dimensions, weight
diameter: 126 mm, height: 65 mm, 200 g
Complies with
EN 54-7, EN 54-5 class A2, EN 54-25,
ETSI EN 300220, EN 50130-4, EN 55022, EN 60950-1
Can be operated according to
ERC REC 70-03
1293-CPD-0263
JABLOTRON ALARMS a.s. hereby declares that the JA-80S
is in compliance
with the essential requirements and other relevant provisions of Directives
1999/5/EC and 1989/106/EC. The original of the conformity assessment can be
found at
, Technical support section.
Although this product does not contain any harmful
materials we suggest you return the product to the dealer or directly
to the producer after use.