The JA-65ST wireless combined smoke and heat detector
The JA-65ST wireless combined smoke and heat detector
MLW51501
1:
The
INS
alarm mode jumper sets the reaction of the system.
FIRE
=
alarm is triggered even if the system is disarmed while
INS
= alarm is
triggered only in an armed system. The
INS
jumper only has an effect if
the detector is assigned to control panel. It has no effect when used with
a UC-216 receiver.
Warning: In the INS position, while the system is disarmed, it is not
protecting against fire. This setting also fully disables the optical
and acoustic indication on the detector itself.
2: MEM Alarm memory:
If the event memory is ON at the time of alarm,
alarm LED indication continues even if normal conditions are restored.
The indication can also be terminated by opening the detector cover by
turning it anti-clockwise and activating the tamper sensor. (Indication is
valid only for FIRE settings).
3 and 4: SMOKE / TEMP sensor participation
Optical smoke sensor
: Smoke entry into the detector is indicated as a
pre-alarm state by the LED flashing. If the smoke threshold density is
exceeded, a siren sound is generated (indication is valid only for FIRE
settings).
Heat sensor:
indication logic is equal to that of the smoke sensor.
Whenever the detector cover is opened, a tamper signal is sent.
Fire alarm
Optical detector:
When smoke penetrates into the detector, the
detector starts flashing red and sending an alarm signal.
Heat detector:
When the temperature reaches the set limits, the
detector starts flashing red and sending an alarm signal.
Alarm memory:
If it is enabled, alarm indication with flashing
continues for a further 30 minutes even when the smoke clears. The
indication can also be terminated by opening the detector cover by
turning it anti-clockwise and activating the tamper sensor.
Note: activation of this function is required by the safety standard.
Tamper alarm:
When the detector cover is opened, the detector sends
a tamper signal.
Detector testing and maintenance
The functioning of the detector can be tested with a special spray
designed for smoke detector testing to simulate fire.
The test should be
carried out once in 30 days
. The detector’s cover should be cleaned
regularly from dust.
Warning: never test the detector with fire.
Battery replacement
The system sends a report automatically when the battery is low.
Optical indication then flashes briefly once every 30 seconds. Remember
to switch the system to Service mode before changing the batteries
(otherwise a tamper alarm will be triggered). It is always essential to
replace all three batteries. Use the same type and the same brand for all
three. When all batteries have been inserted into the detector, a test is
carried out automatically. The test checks the battery voltage and the
sensor status and the information is then sent to the control panel.
Fault indication
The detector checks its functioning. If it detects a fault, its Optical
indication starts flashing rapidly for 1 minute and then it flashes briefly
three times every 30 seconds. In such a case, take out the battery for 1
minute and then insert it again. If the LED indicator starts flashing again
after 1 minute, send the detector to a service centre.
Technical specifications
Power
3 x AA 1.5 V; 2.4 Ah alkaline batteries
Typical lifetime
approx. 3 years
Communication band
433.92 MHz, Jablotron protocol
Communication range
approx. 100 m (unrestricted area)
Smoke detection
optical light scattering
Smoke detector sensitivity
m = 0.11 - 0.13 dB/m according to EN 54-7
Heat detection
class A2 according to EN 54-5
Alarm temperature
+60°C to +70°C
Operating temperature range
-10°C to +80°C
Dimensions
diameter 126 mm, height 50 mm
Complies with
EN 54-5, EN 54-7, EN 54-25,
Also complies with
EN 300220, EN 50130-4,EN 55022, EN 60950-1
Can be operated according to
ERC REC 70-03
1293-CPD-0252
JABLOTRON ALARMS a.s. hereby declares that the JA-65ST detector is in compliance
with the essential requirements and other relevant provisions of Directives 1989/106/EC
and 1999/5/EC. The original of the conformity assessment can be found at
www.jablotron.com
- Technical Support section
Note:
Although this product does not contain any harmful materials we
suggest you return the product to the dealer or directly to the producer
after use. For more detailed information visit
www.jablotron.com
.