background image

The JA-65ST wireless combined smoke and heat detector 

 The JA-65ST wireless combined smoke and heat detector  

 

MLW51503 

1:

 The 

INS

 alarm mode jumper sets the reaction of the system. 

FIRE

 = 

alarm is triggered even if the system is disarmed while 

INS

  = alarm is 

triggered only in an armed system. The 

INS

 jumper only has an effect if 

the detector is assigned to control panel. It has no effect when used with 

a UC-216 receiver.  

Warning: In the INS position, while the system is disarmed, it is not 

protecting against fire.  This setting also fully disables the optical 

and acoustic indication on the detector itself. 

2: MEM Alarm memory: 

If the event memory is ON at the time of alarm, 

alarm LED indication continues even if normal conditions are restored. 

The indication can also be terminated by opening the detector cover by 

turning it anti-clockwise and  activating the tamper sensor. (Indication  is 

valid only for FIRE settings).  

3 and 4: SMOKE / TEMP sensor participation 

Optical smoke sensor

: Smoke entry into the detector is indicated as a 

pre-alarm state by the LED flashing. If the smoke threshold density is 

exceeded, a siren sound is generated (indication is valid only for FIRE 

settings). 

Heat sensor:

 indication logic is equal to that of the smoke sensor. 

Whenever the detector cover is opened, a tamper signal is sent. 

 

 

Fire alarm 

Optical detector:

  When  smoke penetrates into the detector, the 

detector starts flashing red and sending an alarm signal. 

Heat detector:

  When the temperature reaches the set limits, the 

detector starts flashing red and sending an alarm signal. 

Alarm memory: 

  If it is enabled, alarm indication with flashing 

continues for a further 30 minutes even when the smoke clears.  The 

indication can also be terminated by opening the detector cover by 

turning it anti-clockwise and activating the tamper sensor. 

Note: activation of this function is required by the safety standard. 

Tamper alarm:

 When the detector cover is opened, the detector sends 

a tamper signal. 

 

Detector testing and maintenance 

The functioning of the detector can be tested with a special spray 

designed for smoke detector testing to simulate fire. 

The test should be 

carried out once in 30 days

. The detector’s cover should be cleaned 

regularly from dust. 

 

Warning: never test the detector with fire. 

Battery replacement 

The system sends a report automatically when the battery is low. 

Optical indication then flashes briefly once every 30 seconds. Remember 

to switch the system to Service mode before changing the batteries 

(otherwise a tamper alarm will be triggered). It is always essential to 

replace all three batteries. Use the same type and the same brand for all 

three. When all batteries have been inserted into the detector, a test is 

carried out automatically. The test checks the battery voltage and the 

sensor status and the information is then sent to the control panel. 

Fault indication 

The detector checks its functioning. If it detects a fault, its Optical 

indication starts flashing rapidly for 1 minute and then it flashes briefly 

three times every 30 seconds. In such a case, take out the battery for 1 

minute and then insert it again. If the LED indicator starts flashing again 

after 1 minute, send the detector to a service centre. 

Technical specifications 

Power 

3 x AA 1.5 V; 2.4 Ah alkaline batteries

 

Typical lifetime  

approx. 3 years

 

Communication band 

 433.92 MHz, Jablotron protocol

 

Communication range 

approx. 100 m (unrestricted area)

 

Smoke detection 

optical light scattering

 

Smoke detector sensitivity 

 m = 0.11 - 0.13 dB/m according to EN 54-7

 

Heat detection 

class A2 according to EN 54-5

 

Alarm temperature 

+60°C to +70°C

 

Operating temperature range 

-10°C to +70°C

 

Dimensions 

diameter 126 mm, height 50 mm

 

Complies with 

EN 54-5, EN 54-7, EN 54-25,

 

Also complies with 

ETSI EN 300220, EN 50130-4,  

 

EN 55022, EN 60950-1 

Can be operated according to 

ERC REC 70-03

 

 

1293-CPD-0252

 

JABLOTRON ALARMS a.s. hereby declares that the JA-65ST is in a compliance with 

the relevant Union harmonisation legislation: Directives No: 2014/53/EU, 2014/35/EU, 

2014/30/EU, 2011/65/EU. The original of the conformity assessment can be found at 

www.jablotron.com - Section Downloads.

 

 

Note:

 Although this product does not contain any harmful materials we 

suggest you return the product to the dealer or directly to the producer 

after use.

 

 

Reviews: