H-915  installation manual   

11/3 

TBT502 01 

2  ARM

 - (Yellow, Green and Red LEDs) if this LED is off, the system is disarmed. If it is yellow and slowly  blinking, it 

indicates an  Exit delay. A continuously  lit yellow LED indicates that the system is fully armed.  A Rapidly  blinking yellow 
LED indicates an Entrance delay. 
A Slow blinking green LED indicates an Exit delay for the AT HOME arming (only if AUTO AT HOME function enabled). A 
continues green light indicates that system is AT HOME armed. A rapidly blinking green LED indicates an Entrance delay 
for AT HOME arming. 
A red blinking means an alarm condition on the control panel (PANIC alarm is not indicated). 

 

3  ERROR

 - (Red LED) continuously lit indicates system is in the programming mode.  Slow blinking indicates either 

a power supply failure or memory of a Technical alarm. Rapidly  blinking confirms programming of bypass. 

 

4,5,6  ZONE STATUS LEDs: FIRE, TAMPER, 1 to 6: 

When on in the normal operating mode, a lit LED indicates 

a triggered input. Slow blinking zone LED means alarm memory information. It can be reset by  rearming or entering 
[

][3]. 

Rapidly blinking zone LED during exit delay indicates if a zone has been bypassed. 

 

7  Keypad: 

All    control panel functions can be controlled by or programmed with the keypad. Pressing the [#] key 

erases the input buffer (stops the programming)  and acts as an ESC function. The input buffer can also be erased if an 
incorrect or incomplete entry is made (after 20 seconds). 

 

WIRING 

 

Zone inputs:  
TAMP, FIRE, L1 to L6

 and 

COMM

 terminals All zone inputs are supervised End Of Line (EOL) resistor circuits.  Each 

input must be terminated with a 10K ohm EOL resistor to any of the COMM terminals. An input will be triggered if a 
normally open contact is used to short across the EOL resistor. An input is also triggered if normally closed contacts 
wired in series with EOL resistor are opened (see the wiring diagram). 
The Fire alarm is activated if a detector connected to a FIRE input is triggered. The Tamper alarm can  be triggered 
either by the built in tamper switch (control panel & keypads) or by the tamper switches connected to the TAMP input. 
The  definition of zone 1 to 6  (delay, instant, 24hr., fire etc.) can be programmed from the keypad using the [

] [6] 

installer programming mode. 

NOTE: None of the COMM terminals can  be connected to the GND or any other control panel terminal. Such 
a connection will trigger all zone inputs. 

 

Outputs: 

 

E.SIR 

terminal is for connection of the external siren (use piezo siren SA-105 or SA-107). The function of this output is 

programmable for different alarm types (using the [

] [6] installer programming mode).

 

This output is switched to GND  

with a NPN switching transistor when activated. Maximum load can be 500mA. 

 

+SIR

 terminal is the 12V power output for sirens (external and internal), max. 1A (built in fuse FU4). 

 

 The following four output terminals are closed to the GND with a NPN switching transistor when activated. Maximum 
load of each output is 200mA. A 10 ohm current limiting resistor is connected in series with the switching transistor. 
A small relay, buzzer, siren or other DC operated device may be connected between the +12V terminal and each of the 
above output terminals. 

 

I.SIR

 terminal is the  output for the internal siren (use piezo siren SA-105 or SA-107). The function of this output is 

programmable for different alarm types (using the [

] [6] installer programming mode). Model H-915C has built in internal 

sirens connected via a connector. 

 

FIRE

 output is active for alarm period if alarm is triggered by a fire input(s). 

 

ARM

 output is active while the control panel is armed (no matter if in FULL arming or AT HOME arming position). 

 

PANIC

 output is active for alarm period if the PANIC or any silent alarm loop is triggered. 

 

Summary of Contents for HESTIA H-915C

Page 1: ...Security Alarm Control Panel HESTIA 915 installation manual ...

Page 2: ...uired 12V from 1 2Ah to 40Ah stand by consumption 25mA back up power output 12V max 500mA inputs eight loops FIRE TAMPER and 6 fully programmable loops type of loops balanced with End Of Line resistor 10k remote control inputs digital bus for external keypads programmable optional pulse input outputs overswitching relay contact 1A at 60 V external siren output 0 5A at 12 V backup siren output BS f...

Page 3: ...nput is also triggered if normally closed contacts wired in series with EOL resistor are opened see the wiring diagram The Fire alarm is activated if a detector connected to a FIRE input is triggered The Tamper alarm can be triggered either by the built in tamper switch control panel keypads or by the tamper switches connected to the TAMP input The definition of zone 1 to 6 delay instant 24hr fire...

Page 4: ... 5 can be used connect all of them in parallel Check carefully that you have connected corresponding wires before you turn on the power to the control panel The built in keypad on the H 915C model is connected via INT KEY connector Control panel TAMPER There is a tamper switch to protect the housing of the control panel If you have only the H 915B main board don t forget to install the attached ta...

Page 5: ...on was enabled in the installer programming level If quick arming is enabled the H 915 can be AT HOME armed by entering only the 9 command DISARMING Enter a valid access code to disarm If the chime jumper in the H 915K keypad is connected and you triggered a sensor in a delay zone the keypad buzzer will be beeping In such a case you have only a limited amount of time entrance delay to enter a vali...

Page 6: ...atically in the moment when used once for arming NOTE If you press 9 in user programming level the H 915 control panel will send information about events history to the special serial interface printer which can be connected to the keypad terminals as an option Only code number 0 master code is programmed from factory the other access codes are blank 6 INSTALLER CODE Entering of INSTALLER PROGRAMM...

Page 7: ...If the premises is entered without coming through a delay entrance and a next delay loop is triggered an immediate intruder alarm will be generated 05 24Hr silent loop operates as the type 01 but it triggers the PANIC alarm 06 Instant silent loop operates as the type 02 but it triggers the PANIC alarm 07 Delay silent loop operates as the type 03 but it triggers the PANIC alarm 08 Interior instant ...

Page 8: ...rmed by both sirens The y can only be from 0 to 3 4 1y External arming control with loop 6 input If y 0 zone input 6 will work as programmed in section 1 If y 1 than zone input works as input for external arming and disarming If you close this input with E O L resistor for a moment it will have the same function as entering of a valid access code By doing this the control panel can be armed disarm...

Page 9: ...l will start in the alarm condition when the power is switch on again If there is any reason to switch the power completely off for example when you want to extend the system with an optional device we recommend to enter the installer programming level at first FACTORY DEFAULT SETTING Master Code 1234 Installer Code 1010 No other access codes programmed Zone definition 1 delay 2 next delay interio...

Page 10: ...F 3 ON ON OFF 4 OFF OFF ON 5 ON OFF ON 6 OFF ON ON 7 ON ON ON For Panic alarm y can only be 0 or 2 Panic alarm always activates Panic o Fire alarm aiways activates Fire out ES Ext Siren IS Int Siren 3 xy Alarm outputs definition x alarm default otputs programmed enter y 0 technic Relay 3 0 _ 1 fire ES IS Relay Fire 3 1 _ 2 intruder ES IS Relay 3 2 _ 3 panic Panic 3 3 _ 4 xy System option functions...

Page 11: ...USER S OPERATION GUIDE OF H 915 Zone location No protected area zone type 1 2 3 4 5 6 Tamper Fire Exit Entry Alarm if troubles call your installer phone H 915 installation manual 11 11 TBT502 01 ...

Page 12: ...H 915 installation manual 11 12 TBT502 01 ...