JABLOTRON FUTURA

SYSTEM DESIGN GUIDE

Page 10/16

JABLOTRON LIVING TECHNOLOGY

4

4 .. 2

2 .   

.    In st a lla t ion

In st a lla t ion

C o n d e n s a t e   d r a i n   c o n n e c t i o n

C o n d e n s a t e   d r a i n   c o n n e c t i o n

In the heat exchanger, the exhausted air is cooled by the supplied air causing moisture condensation. The resulting condensed water is drained

towards the siphon. The condensate drain connection is found at the bottom side of the heat recovery unit. A siphon, which is connected to the

sewerage system, must be mounted onto the coupling of the condensate drain connection (HT 32 mm (1.26") drain pipe).

C o n d e n s a t e   m u s t   b e   a l l o w e d   t o   f r e e l y   f l o w   o u t   o f   t h e   h e a t   r e c o v e r y   u n i t   b y   g r a v i t y !

C o n d e n s a t e   m u s t   b e   a l l o w e d   t o   f r e e l y   f l o w   o u t   o f   t h e   h e a t   r e c o v e r y   u n i t   b y   g r a v i t y !

Re c o m m e n d e d   t o p o l o g y   o f   c o n n e c t i n g   p e r i p h e r a l s   t o   RS - 4 8 5   b u s  

Re c o m m e n d e d   t o p o l o g y   o f   c o n n e c t i n g   p e r i p h e r a l s   t o   RS - 4 8 5   b u s  

This  RS-485  bus  is  intended  to  connect  only  the  peripherals  of  the  Futura  heat  recovery  unit.  The  bus  is  four-wire,  with  a  24  V  supply  and  a

maximum total current of 500 mA. The power supply is resistant to overload or short circuit.

Připojeno

přes

RS485

Montážní krabice JA-190PL

+ rozbočovač JA-110Z-B

O v la d a č e  a  s e n z o ry  C O ₂

Klapky zónového větrání - přívod

Předokládaná dostupnost v roce

2020 i pro zpětnou doinstalaci.

Klapky zónového větrání - odtah

Figure 8: Connection topology

Re c o m m e n d e d   c a b l e

Re c o m m e n d e d   c a b l e

Four-wire twisted-pair cable, eg. Unitronic PAAR LiYCY 2 × 2 × 0,34 – 0,5 mm

2

 or J-Y(St)Y 2 × 2 × 0,8 mm

2

. It is possible to use UTP or STP cable.

The cable must not run parallel to low or high voltage power lines. Occasional crossing is fine.

B u s   t e r m i n a t i n g   r e s i s t o r s   RS - 4 8 5

B u s   t e r m i n a t i n g   r e s i s t o r s   RS - 4 8 5

The terminating resistor 120R is connected at the heat recovery unit. It is recommended to connect a second terminating resistor at the most

remote controller or sensor. . For more convenient wiring, a Jablotron JA-110Z-B RS-485 bus splitter and JA-190PL box can be used. In the case of

a large number of devices and a long wiring in a star connection, a suitable hub must be used.

E n t h a l p y   c o o l i n g / h e a t i n g   m o d u l e   C o o l B r e e z e

E n t h a l p y   c o o l i n g / h e a t i n g   m o d u l e   C o o l B r e e z e

The CoolBreeze add-on module requires c o n n e c t i o n   o f   t h e   o u t d o o r   c o n d e n s a t i o n   u n i t   t o   t h e   m a i n s   w i t h   a   f i x e d   2 3 0 V   /   5 0 H z ,

c o n n e c t i o n   o f   t h e   o u t d o o r   c o n d e n s a t i o n   u n i t   t o   t h e   m a i n s   w i t h   a   f i x e d   2 3 0 V   /   5 0 H z ,

t y p e   B   1 6 A  f u s e   a n d   a   3 0 0   m A  r e s i d u a l   c u r r e n t   c i r c u i t   b r e a k e r

t y p e   B   1 6 A  f u s e   a n d   a   3 0 0   m A  r e s i d u a l   c u r r e n t   c i r c u i t   b r e a k e r .  Alternatively,  preparation  for  later  installation  of  the  CoolBreeze

module can be made.

The internal evaporator of the CoolBreeze module is connected to the outdoor unit with a 4   x   0 .7 5   m m  

4   x   0 .7 5   m m  

2

2

   communication cable. The refrigerant

piping should be 6/10 mm

2

. A minimum coolant pipe length of 5 m (16.4 ft) and no longer than of 15 m (49 ft) must be guaranteed.

Summary of Contents for FUTURA L

Page 1: ......

Page 2: ......

Page 3: ...and output characteristics of the unit 2 CoolBreeze cooling output characteristics 3 CoolBreeze heating output characteristics 4 Acoustic parameters 5 Leakage 6 Heat recovery efficiency 7 VAC scheme 3...

Page 4: ...used approximately once every 2 6 months The filtration can be supplemented with an optional accessory in the form of a carbon filter which is inserted directly into the unit under the supply air fil...

Page 5: ...ency 91 8 91 4 Acoustic power level Lwa 46 dBa 46 dBa Reference flow 175 m3 h 6180 cubic feet per hour 245 m3 h 8652 cubic feet per hour Reference pressure difference 50 Pa 50 Pa SPI 0 34 W m3 h 0 33...

Page 6: ...ed with a wall mounted control with an integrated CO2 sensor 1 piece as standard Integration in the MyJABLOTRON app which supports easy control of all the user functions and settings remote monitoring...

Page 7: ...2 lbs Power input Cooling mode 460 W heating mode 660 W Refrigerant piping Min 5m 16 4 ft max 20m 66 ft The outdoor unit is pre filled to 15m pipe In case of extension add 20g m pipe Maximum height d...

Page 8: ...racteristics Measured at outdoor temperature 34 C 93 F and 55 relative humidity and indoor temperature 25 C 77 F and 65 relative humidity 2 3 CoolBreeze heating output characteristics Figure 3 CoolBre...

Page 9: ...ns 328 x 309 x 48 mm 12 9 x 12 2 x 1 9 Acoustic power level L dB Frequency Hz Total 63 125 250 500 1k 2k 4k 8k Air supply 51 6 41 6 44 4 27 6 22 0 29 1 15 9 10 4 23 8 Air exhaust 52 0 42 1 45 0 27 9 2...

Page 10: ...GUIDE Page 8 16 JABLOTRON LIVING TECHNOLOGY 2 5 Leakage Figure 4 Internal leakage blue and external leakage red compared to certification limit green 2 6 Heat recovery efficiency Figure 5 Heat recove...

Page 11: ...tion requirements 4 1 Connection of ventilation pipes OA Outdoor air 150 inner 210 outer EPP pipes EA Exhaust air 150 inner 210 outer EPP pipes SA Supply air 150 SONOCUT silencer RA Residual air 150 S...

Page 12: ...z nov ho v tr n odtah Figure 8 Connection topology Recommended cable Four wire twisted pair cable eg Unitronic PAAR LiYCY 2 2 0 34 0 5 mm2 or J Y St Y 2 2 0 8 mm2 It is possible to use UTP or STP cabl...

Page 13: ...N LIVING TECHNOLOGY 5 Energy label 2017 1254 2014 46 dB I II 3 JABLOTRON LIVING TECHNOLOGY CZ s r o Futura A A B C D E F G A 250 m h 2017 1254 2014 46 dB I II 350 m3 h JABLOTRON LIVING TECHNOLOGY CZ s...

Page 14: ...CB pou t p rubu z jednotky Futura Vstup v stup chladiva pro CoolBreeze Hadice DN32 Napojen na kanalizaci P i instalaci zachovat minim ln prostor 330mm vzd lenost pro nasazen EPP kolena Vzd lenost hra...

Page 15: ...N FUTURA SYSTEM DESIGN GUIDE Page 13 16 JABLOTRON LIVING TECHNOLOGY Main dimensions incl CoolBreeze module 200 18 59 444 60 33 524 P ed jednotkou je nutn ponechat prostor min 500mm pro pohodlnou v m n...

Page 16: ...JABLOTRON FUTURA SYSTEM DESIGN GUIDE Page 14 16 JABLOTRON LIVING TECHNOLOGY Mounting dimensions for wall mounting 227 5 1 0 1 6 6 0 540 227 5...

Page 17: ...15 16 JABLOTRON LIVING TECHNOLOGY 7 Dependence of air flow and external pressure Futura M Figure 10 Dependence of air flow m3 h and external pressure Pa Futura M Futura L Figure 11 Dependence of air f...

Page 18: ...JABLOTRON FUTURA SYSTEM DESIGN GUIDE Page 16 16 JABLOTRON LIVING TECHNOLOGY 8 CoolBreeze pressure loss Figure 12 CoolBreeze pressure loss Pa at air flow m3 h...

Page 19: ......

Page 20: ......

Reviews: