JABLOTRON FUTURA
SYSTEM DESIGN GUIDE
Page 10/16
JABLOTRON LIVING TECHNOLOGY
4
4 .. 2
2 .
. In st a lla t ion
In st a lla t ion
C o n d e n s a t e d r a i n c o n n e c t i o n
C o n d e n s a t e d r a i n c o n n e c t i o n
In the heat exchanger, the exhausted air is cooled by the supplied air causing moisture condensation. The resulting condensed water is drained
towards the siphon. The condensate drain connection is found at the bottom side of the heat recovery unit. A siphon, which is connected to the
sewerage system, must be mounted onto the coupling of the condensate drain connection (HT 32 mm (1.26") drain pipe).
C o n d e n s a t e m u s t b e a l l o w e d t o f r e e l y f l o w o u t o f t h e h e a t r e c o v e r y u n i t b y g r a v i t y !
C o n d e n s a t e m u s t b e a l l o w e d t o f r e e l y f l o w o u t o f t h e h e a t r e c o v e r y u n i t b y g r a v i t y !
Re c o m m e n d e d t o p o l o g y o f c o n n e c t i n g p e r i p h e r a l s t o RS - 4 8 5 b u s
Re c o m m e n d e d t o p o l o g y o f c o n n e c t i n g p e r i p h e r a l s t o RS - 4 8 5 b u s
This RS-485 bus is intended to connect only the peripherals of the Futura heat recovery unit. The bus is four-wire, with a 24 V supply and a
maximum total current of 500 mA. The power supply is resistant to overload or short circuit.
Připojeno
přes
RS485
Montážní krabice JA-190PL
+ rozbočovač JA-110Z-B
O v la d a č e a s e n z o ry C O ₂
Klapky zónového větrání - přívod
Předokládaná dostupnost v roce
2020 i pro zpětnou doinstalaci.
Klapky zónového větrání - odtah
Figure 8: Connection topology
Re c o m m e n d e d c a b l e
Re c o m m e n d e d c a b l e
Four-wire twisted-pair cable, eg. Unitronic PAAR LiYCY 2 × 2 × 0,34 – 0,5 mm
2
or J-Y(St)Y 2 × 2 × 0,8 mm
2
. It is possible to use UTP or STP cable.
The cable must not run parallel to low or high voltage power lines. Occasional crossing is fine.
B u s t e r m i n a t i n g r e s i s t o r s RS - 4 8 5
B u s t e r m i n a t i n g r e s i s t o r s RS - 4 8 5
The terminating resistor 120R is connected at the heat recovery unit. It is recommended to connect a second terminating resistor at the most
remote controller or sensor. . For more convenient wiring, a Jablotron JA-110Z-B RS-485 bus splitter and JA-190PL box can be used. In the case of
a large number of devices and a long wiring in a star connection, a suitable hub must be used.
E n t h a l p y c o o l i n g / h e a t i n g m o d u l e C o o l B r e e z e
E n t h a l p y c o o l i n g / h e a t i n g m o d u l e C o o l B r e e z e
The CoolBreeze add-on module requires c o n n e c t i o n o f t h e o u t d o o r c o n d e n s a t i o n u n i t t o t h e m a i n s w i t h a f i x e d 2 3 0 V / 5 0 H z ,
c o n n e c t i o n o f t h e o u t d o o r c o n d e n s a t i o n u n i t t o t h e m a i n s w i t h a f i x e d 2 3 0 V / 5 0 H z ,
t y p e B 1 6 A f u s e a n d a 3 0 0 m A r e s i d u a l c u r r e n t c i r c u i t b r e a k e r
t y p e B 1 6 A f u s e a n d a 3 0 0 m A r e s i d u a l c u r r e n t c i r c u i t b r e a k e r . Alternatively, preparation for later installation of the CoolBreeze
module can be made.
The internal evaporator of the CoolBreeze module is connected to the outdoor unit with a 4 x 0 .7 5 m m
4 x 0 .7 5 m m
2
2
communication cable. The refrigerant
piping should be 6/10 mm
2
. A minimum coolant pipe length of 5 m (16.4 ft) and no longer than of 15 m (49 ft) must be guaranteed.