Use and Maintenance 

The system doesn´t require any special maintenance in operational 

mode. Before the heating time starts, we recommend you to replace the 
batteries in the wireless devices (the declared lifetime for thermostats is 
1year, with 2 years for detectors.). When any device reports a Low batt 
condition, then the unit indicates this by a relevant LED. The device still 
works, but it is strictly recommended to replace the battery in 14 days. 

If the outputs from 1-16 have not been active for 7 days, then they are 

switched on one after the other for 15 min because of protection against 
the clogging of the thermo-electric valves. The circulation pump relay 
output terminals switch each 7 days for 10 minutes. 

Each device (thermostats, detectors) sends periodical transmissions. If 

the AC-116 doesn´t receive them, then it starts to indicate communication 
lost (by a flashing green LED on a specific channel). If all the devices 
enrolled to the specific channel are lost then this channel is switched on 
every one hour for 15 minutes. 

In the case of troubles with lost communication first check the 

environment and avoid the negative influence of any other radio device. 
This causes a communication loss with more than one device at the 
same time. Move the device to a better place if only this particular 
device’s communcation is lost. 

Notes: 

-  Anti-clogging protection works independently of the “ON” channel 

status and even if a device has no communication with the main unit 

The clogging protection time schedule of output channels 1-16 can 
be adjusted by the AC-100LCD touchscreen

 

 
Caution:

 the producer shall not be held responsible if the 

system has been installed or set up incorrectly. 

Technical specifications 

Power 

230 V AC, 50 Hz 

Current consumption 

0.02 A standby; 0.3 A max. 

Maximum output current 

1.6 A 

Built in current protection 

fuse, 1,6 A 

Maximum allowed relay load 

10 A / 230 V 

Voltage for outputs 1–16 

24 V DC 

Load for outputs 1–16 

max. 0.4 A for each output, 

 

1,6 A for sum of all outputs 

Communication band 

868.1 MHz 

RF range receiver/transmitter 

100 m (open area)

 

Maximum no. of devices 

48 

Dimensions: 

400 x 100 x 60 mm 

Mechanical resistance (EN 62262) 

IK06: 

Housing (EN 60529) 

 

IP-30 

Operational environment: 

general indoor, relative humidity max. 85 % 

Operational temperature (environment):  

-10

C to +40

o

Radio parameters: 

 

ETSI EN 300 220 

EMC: 

EN 50130-4, EN 55022 

Safety:  

EN 

60730-1 

Can be operated to: 

ERC REC 70-03

 

 

JABLOTRON ALALRMS a.s. hereby declares that the   
AC-116  is in compliance with the essential requirements and 
other relevant provisions of Directive 1999/5/EC. The 
original of the conformity assessment can be found at 

www.jablotron.com

 - Technical Support section. 

 