Light status 6)
Fault type
Designation
CHARGING COMPLETED
ERROR
Charger
fault:
ERROR
flashes
continuously
OFF
OFF
Prolonged flash Mains voltage too low Contact electrician 1)
ON
OFF
Prolonged flash Fault in charger
Contact charger supplier
Battery
fault:
Group
flash with
ERROR
OFF
OFF
2 flashes
Battery fault:
Charging when
significantly depleted
not possible
Contact battery supplier 3)
OFF
ON
3 flashes
Battery fault: Fault
during charging with
falling current -
battery defect
Contact battery
supplier 3)4)
OFF
ON
4 flashes
Battery fault: Main
charging time too
long. Battery defect
or charger too small
in relation to battery
capacity
Contact battery
supplier 3)4)
OFF
ON
5 flashes
Battery fault: Battery
voltage too high
System fault 2)
External
error
source:
Group flash
with
ERROR
OFF
OFF
6 flashes
Charger temperature
too high
Check that the charger is
positioned so that there is 5
cm of free space on all sides
OFF
OFF
ON
No battery connected Standby mode 5)
Figure 2: Signaling of faults
1)
Always possible - charging will recommence once the mains voltage is OK.
2)
During start-up.
3)
During charging (- No standby charging in the event of a fault!)
4)
Available capacity filled.
5)
In the event of any interruption (fault!) to the charging process, the connection of an
incorrectly polarized battery or an attempt to charge batteries using an off-load voltage below
3V, ERROR will remain lit (steady) when connecting a charging plug.
6)
ON: Light lit
OFF: light not lit
4