background image

 

 

 

Figure 3:  SSAC timer setup 

 

Figure 3 shows an SSAC timer set for 1 

coin to start

 and 3.8

 

minutes per coin

 for a total run time of 3.8 minutes (3 minutes 

and 48 seconds). 

 

TIMER SETUP – SSAC TIMERS 

 

Note:  “AE” and “AN” model SSAC timers are accumulating 
timers. During use, timing can be extended proportionately 
by adding more coins. 

The SSAC timer has two adjustable settings:  Time per coin (in 

minutes) and number of coins to start.   

 

Time per coin: 
Time per coin
 is the amount of time the unit will run per coin 

inserted and can be set from 0.1 minutes (6 seconds) to 12.7 
minutes (12 minutes and 42 seconds)
 in increments of 6 seconds 
by turning on the correct switches until their values equal the 
desired time.  Refer to Tables 2 and 3 (pages 11-12) for standard 
timer and coin settings.  For custom settings, follow the steps 
below: 
 

1.

 

Figure the total time your vac will run (in minutes) and divide 
that number by the number of coins to start.  This is your 

time per coin.  Round up or down to the nearest tenth of a 
minute. 

2.

 

Subtract the largest value switch (initially 6.4) from your time 
per coin
.  

a.

 

 If the resulting number is zero, move the switch to 
the “on” position and set all remaining un-set switches 
in the “off” position.  Your timer is now set. 

b.

 

 If the resulting number is positive, move the switch 
into the “on” position.  Using the resulting number as 
your new time per coin, repeat step 2 with the next 
largest switch value. 

c.

 

If the resulting number is negative, set the switch in 
the “off” position and repeat step 2 using the next 
largest switch value. 

Coins to start: 

Coins to start is the amount of coins needed to activate the 
timer and can be set from one to seven coins in increments of 

one coin.  Refer to Table  
2 (page 10) for switch settings 

Summary of Contents for 8670 Series

Page 1: ...8670 SERIES MANUAL ...

Page 2: ...TION 5 WIRING INFO 6 MOUNTING DIMENSIONS 6 TIMER SETUP 7 10 SSAC SETUP 7 INFITEC SETUP 8 TIMER SETTINGS CHART 9 TYPICAL TIMER SETTINGS 10 MAINTENANCE 11 PARTS BREAKDOWN 12 13 AIR MACHINE WATER 12 REEL BASE 13 SCHEMATICS 14 15 8670 SERIES WITH SSAC 14 8670 SERIES WITH INFITEC ASCR54 15 BASIC TROUBLESHOOTING 16 8670 SERIES MANUAL 8 4 10 ...

Page 3: ...ber can be found on the tag that comes attached to the keys There may be more than one key number depending on unit Please keep this information with your records MODEL _________________________________________ SERIAL _________________________________________ KEY NUMBER S _________________________________ DATE PURCHASED _______________________________ DISTRIBUTOR __________________________________...

Page 4: ...__________________________________________________ Air specifications Compressor Dependant on Model ordered Thomas 120vac 60hz hp twin head Thomas 120vac 60hz hp non twin head Devilbiss 120vac 60hz 1 hp Gast 120vac 60hz hp twin head Timer SSAC and Infitec ASCR54 __________________________________________________________________________________________________ Water specifications Solenoid 120vac 6...

Page 5: ...nded use SAVE THESE INSTRUCTIONS Installation Instructions Determine location to mount unit DANGER THIS EQUIPMENT INCORPORATES PARTS SUCH AS SWITCHES MOTORS OR THE LIKE THAT TEND TO PRODUCE ARCS OR SPARKS THAT CAN CAUSE AN EXPLOSION WHEN LOCATED IN GASOLINE DISPENSING AND SERVICE STATIONS INSTALL AND USE AT LEAST 20 FEET 6 M HORIZONTALLY FROM THE EXTERIOR ENCLOSURE OF ANY DISPENSING PUMP AND AT LE...

Page 6: ...6 AIR MACHINE MOUNTING DIMENSIONS ...

Page 7: ...settings For custom settings follow the steps below 1 Figure the total time your vac will run in minutes and divide that number by the number of coins to start This is your time per coin Round up or down to the nearest tenth of a minute 2 Subtract the largest value switch initially 6 4 from your time per coin a If the resulting number is zero move the switch to the on position and set all remainin...

Page 8: ... your total run time Round up or down as desired 2 Subtract the largest value switch initially 512 from your total run time a If the resulting number is zero move the switch to the on position and set all remaining un set switches in the off position Your timer is now set b If the resulting number is positive move the switch into the on position Using the resulting number as your new time per coin...

Page 9: ... 9 54 sec 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 5 3 0 3 5 4 0 4 5 5 0 5 5 6 0 6 5 7 0 7 5 8 0 8 5 9 0 9 5 10 0 0 1 x x x x x x x x x x x x x x x x x x 0 2 x x x x x x x x x x x x x x x x x x 0 4 x x x x x x x x x x x x x x x x x 0 8 x x x x x x x x x x x x x x x x 1 6 x x x x x x x x x x x x x x 3 2 x x x x x x x 6 4 x x x x x x x x 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 x x x x x x x x 2 x...

Page 10: ...IN 2 4 8 256 50 5 MIN 2 4 16 128 50 5 MIN 0 1 0 8 1 6 50 5 MIN 4 8 32 256 50 5 1 2 MIN 2 4 32 128 50 5 1 2 MIN 50 5 1 2 MIN 2 8 64 256 75 2 MIN 8 32 75 2 MIN 75 2 MIN 8 16 32 64 75 2 1 2 MIN 2 16 32 75 2 1 2 MIN 75 2 1 2 MIN 2 4 16 128 75 3 MIN 4 8 16 32 75 3 MIN 0 2 0 8 75 3 MIN 4 16 32 128 75 3 1 2 MIN 2 4 64 75 3 1 2 MIN 75 3 1 2 MIN 2 16 64 128 75 4 MIN 16 64 75 4 MIN 75 4 MIN 16 32 64 128 75 ...

Page 11: ...zle for signs of wear and abuse Replace as needed Clean air cabinet as needed with a non abrasive stainless steel cleaner Examine air hose for cuts or wear and replace as needed Every month remove filter from compressor and clean ...

Page 12: ...12 ...

Page 13: ...13 ...

Page 14: ...TANT 20AMP SERVICE IS REQUIRED FOR DEVILBISS UNITS 18GA BLACK IMPORTANT 10AMP SERVICE IS REQUIRED FOR TWIN THOMAS GAST UNITS THOMAS BLUE GAST WHITE DEVILBISS WHITE TO COMPRESSOR TO COMPRESSOR 120 VAC HOT 120 VAC GROUND 8124B001 8712SS5 8673 9 5914 B C A D G F H E WATER SOLENOID BLACK BLACK TO NO TO B ONLY USED WITH UNITS WITH WATER FEATURE 8697 8726 SWITCH CONNECTIONS ARE THE BLUE WIRES CURRENTLY ...

Page 15: ...20AMP SERVICE IS REQUIRED FOR DEVILBISS UNITS 18GA BLACK IMPORTANT 10AMP SERVICE IS REQUIRED FOR TWIN THOMAS GAST UNITS THOMAS BLUE GAST WHITE DEVILBISS WHITE TO COMPRESSOR TO COMPRESSOR 120 VAC HOT 120 VAC GROUND 8124B001 8673 9 5914 B C A D G F H E WATER SOLENOID BLACK BLACK TO 2 TO 3 ONLY USED WITH UNITS WITH WATER FEATURE 8697 8726 SWITCH CONNECTIONS ARE THE BLUE WIRES CURRENTLY SHOWN GOING TO...

Page 16: ...OR CHECK AIR CHUCK TO MAKE SURE NO DEBRIS IS AIR PATH ALSO CHECK ORING AROUND AIR CHUCK IS IT BLOCKING THE AIR PATH IS IT UNLOADING ALL THE TIME SLEEVE IN COMPRESSOR MAY BE PITTED OR SCRATCHED UP PISTON ORING MAY BE WORN OR DAMAGED DEBRIS IN VALVE PLATE OPENING IS NOT ALLOWING IT TO SHUT REPAIR KIT MAY BE NEEDED WARNING Disconnect Power before Servicing WARNING Disconnect Power before Servicing ...

Reviews: