5. Insert the lamp back into the quartz sleeve until the spring resists further
travel. Gently push down and twist the lamp connector a quarter turn
clockwise - the bayonet fitting will hold the lamp holder in place.
6. Insert the lamp key into the ballast controller.
7.
Reconnect the earth wire to the chamber tab.
www.jdultrasonics.co.uk
|
+44 (0)1924 378 448
UV DISINFECTION - OPERATING & MAINTENANCE
INITIATE LAMP COUNTDOWN SEQUENCE
After changing the lamp on the system, the controller
must be reset in order for the system to begin its
countdown function on a newly installed lamp. To
perform this reset, firmly depress the button on the
front of the controller and then manually power up the
unit.
Keep holding down the button for five seconds until the
controller has reset the internal timer. Release the
button and the lamp countdown feature has now been
reset. An audible chirp will be heard as well as the
“lamp life reset” screen.
Atlas UV
Atlas UV
Atlas UV
lamp life reset
continue holding
button to reset
lamp timer
5s
screens during reset
2
1
sonicom™
J D UltraSonics