− 19 −
2-2 Setting
• Initial screen (At power on)
PUMP CONTROLLER
IWAKI PUMPS
After indicated on screen, it scrolls automatically to screen No.1.
• Setting screen No.1 (Setting the pump drive system)
1. DRIVE MODE
SENSOR? TIMER?
• The setting object mode is flickering.
• Select the setting object with
key, and enter by
key.
A specified flow rate control,Normal operation
→
SENSOR
→
Setting screen No.2
Timer mode
→
TIMER
→
Setting screen No.12
ENTER
SELECT
• Setting screen No.2 (Setting the presence of electro-pneumatic regulator)
2. E−P Reg SET
Yes? No?
• The setting object mode is flickering.
• Select the presence (Y / N) of Electro-pneumatic regulator.
• Select the setting object with
key, and enter by
key.
A specified flow rate control
→
Yes
→
Setting screen No.3
Normal operation
→
No
→
Setting screen No.8
ENTER
SELECT
• Setting screen No.3 (Setting 1 shot discharge capacity of pump)
3. 1Shot d capa.
dc=****.* cc/shot
• Setting 1 shot discharge capacity of pump to ****.* area.
• Set 1 shot discharge capacity of each pump as shown in Chart 8.
• Every time depressing
key, each input value is
sequentially indicated as 1
→
2
→
3
→
........
→
9
→
0
→
1.......
Then the required value can be settled by depressing ENTER key.
After the settlement of the first figure, by depressing ENTER key to
decrease the figure, and then input each required value as the same
step as above.
SELECT
Pump type
Logical value of 1 shot discharge capacity [cc / shot]
FF-10H
93
FF-20H
185
FF-40H
500
FH-10R
85
FH-20R
190
FH-40R
500
FF-10
93
FF-20
204
FA-40VE
500
FW-20
200
FW-40
500
FW-80
1000
FS-15
63
FS-30
138
FS-60
284
Chart 10