Installation
6 720 642 838
(2010/03)
19
7.3
Assembly
B
Press the spacer feet into position on the lower part
of the back of the cooling station. Install the wall
mounting on the wall and hang the cooling station in
place.
Fig. 15 Installation
7.4
Removing the front panel
B
Place the cooling station so that the front panel can
be removed and the internal components accessed
without any difficulty. Remove the front panel by
unscrewing the two screws on the roof of the cooling
station, tilt the front panel outwards and take it off.
7.5
Connection
B
The following connections must be made on the
cooling station:
•
Flow and return lines cooling water
•
Flow and return lines heat transfer fluid
•
Power supply
•
CAN bus
B
Insulate the heat transfer fluid side pipes to/from the
cooling station against condensation.
B
Make the connections according to the selected
system solution and wiring diagram.
The flow pipes can be thermally insulated to ensure
optimum heating or cooling distribution.
7.5.1
Room sensor (accessory)
The room sensor is an accessory that must be used in
system solutions with cooling.
Installation location requirements:
•
If possible, interior wall without drafts or heat
radiation.
•
Unimpeded circulation of room air under the room
sensor (dotted area in image 16 must be kept clear).
Fig. 16 Recommended installation location for room
sensor.
7.5.2
Room transducer for relative humidity and
temperature (dew point sensor) (accessory)
B
Connect the room transducer for humidity and
temperature using the same principle as for room
sensor ( Chapter 7.5.1).
WARNING:
Install the wall mounting on a
suitable wall using appropriate screws for
the wall material and weight of the cooling
station.
WARNING:
The insulation on the heat
transfer fluid pipes must be full coverage.
6 720 615 125-27.1I
It must be possible to disable the cooling
station electrical connections safely.
B
Install a separate safety switch that cuts
all current to the cooling station.
It is only the room where the room sensor is
located that can influence regulation of the
temperature. ( Chapter 9.2)
If a room sensor is used the dew point
monitor with humidity sensor must be
installed. ( Chapter 9.5)
6 720 615 125-28.1I