12LRN
4 – 1
12LRN
Service Manual
CHAPTER 4.
REFRIGERATION CYCLE
[1] FLOW FOW REFRIGERANT
[2] STANDARD CONDITION
* REFRIGERANT PIPE LENGTH 5m
[3] TEMPERATURE AT EACH PART AND PRESSURE IN 3-WAY VALVE
* On test run mode
Indoor side
Outdoor side
Dry-bulb Temp. (
C)
Relative Humidity (%)
Dry-bulb Temp. (
C)
Relative Humidity (%)
Cooling
27
47
35
40
Heating
20
–
7
87
Model
12LR-N
9LR-N
NO. Condition
Cooling
Heating
Cooling
Heating
Temp. on
(
C)
66
63
66
65
Temp. on
(
C)
40
2
40
2
Temp. on
(
C)
14
22
14
23
Temp. on
(
C)
17
6
16
6
3-way valve pressure (MPaG) 1.05
2.14
1.04
2.23
s
1
4
C
2
Accumulator
3
Strainer
Expansion
valve
Heating
Cooling
Outdoor unit
Condenser
Evaporator
Indoor unit
Reverse valve
Comp-
ressor
Flare coupling
Flare coupling
3-way
valve
2-way
valve
Silencer
Coil
Antifreeze
pipe
Silencer