5.

 

Tighten mounting bolts, making sure actuator is centered on the valve/damper drive shaft.

 

6.

 

Before  applying  power  to  the  unit,  utilize  the  handwheel  (if  supplied)  to  check  for  unobstructed  manual 
operation from fully CW to fully CCW positions. (See “Manual Override” section below.)

 

7.

 

Remove the cover and make the electrical connections as per the wiring diagram. Typical connections have 
AC Neutral or DC (-) to terminal 1 and AC Live or DC (+) to terminal 3 or 4. Connection to terminal 3 to OPEN 
(CCW). Connection to terminal 4 to CLOSE (CW). 

 

8.

 

For  models  where  auxiliary  switches  are  provided,  terminals  A  -  F  are  for  2  x  SPDT  adjustable  auxiliary 
switches. They are dry type Form C, rated 5A @ 250V AC max. Terminals A, B & C are for the OPEN position 
auxiliary switch (adjustable). Terminals D, E & F are for the CLOSE position auxiliary switch (adjustable). 

 

9.

 

Connect the ground wire to PE inside the electric actuator.

 

10.

 

Replace cover and secure cover screws.

 

11.

 

Do NOT apply power at this time. See “Commissioning” section below.

 

12.

 

Check below explanation of Duty Cycle. The intended service should not go above the maximum duty cycle 
as noted on the actuator nameplate.

 

Installation Notes 

 

These  actuators  are  designed  to  be  used  between  a  horizontal  and  upright  position.  Do  NOT  mount  the 
assembly with the actuator top below a horizontal position.

 

 

When installing conduit, use proper techniques for entry into the actuator. It is preferred that the conduit 
entries face downward. Use drip loops to prevent conduit condensate from entering the actuator. Use proper 
fittings to maintain the NEMA 4X integrity of the housing. Seal (pot) the conduit entries.

 

 

Use proper wire size to prevent actuator failure. All terminals accept 12 -18AWG solid/stranded wire.

 

 

Do NOT touch any components on the PCB with metal tools or bare hands.

 

 

The  internal  heater  is  to  be  used  in  all  applications.  Do  NOT  install  the  actuator  outdoors  or  in  humid 
environments, unless it is powered up and the heater is functioning.

 

 

Do NOT parallel wire multiple actuators together without utilizing isolation relays. If this is your intention, 
please contact Innovative Actuation Incorporated for a multiple actuator parallel wiring diagram.

 

 

 

Summary of Contents for IVS A

Page 1: ...Receiving Inspection Carefully inspect for shipping damage Damage to the shipping carton is usually a good indication that it has received rough handing Report all damage immediately to the freight c...

Page 2: ...ate between 0 and 90 Most failsafe quarter turn products will not require recalibration of these settings If any travel adjustment is necessary please refer to the Limit Switch Setting section below 2...

Page 3: ...Commissioning section below 12 Check below explanation of Duty Cycle The intended service should not go above the maximum duty cycle as noted on the actuator nameplate Installation Notes These actuat...

Page 4: ...ide gearbox if supplied compresses the spring as the valve is opened See Photo 4 The unit is shipped without the handwheel assembled as shown in Photo 5 Using the hardware provided thread the socket h...

Page 5: ...ctrical travel limiting device The mechanical end stop MUST always be set before the limit switch settings Ensure that the power is OFF Locate the housing cap see Photo 8 and remove the cap screws usi...

Page 6: ...he open and closed position of the valve The position is set to stop the travel of the actuator when the travel cams activate the limit switch Standard is two limit switches LS1 LS2 one for open one f...

Page 7: ...set screw on cam TC2 o Rotate cam counter clockwise to reset the switch contact o Then slowly rotate cam clockwise until a light click is heard o Securely tighten the cam and apply power to check the...

Page 8: ...oosen the set screw on cam TC4 o Rotate cam counter clockwise to reset the switch contact o Then slowly rotate cam clockwise until a light click is heard o Slowly continue to rotate in the same direct...

Page 9: ...than specified New valve may be required The voltage may be under over rated Check the supply voltage The actuator may be against one of the mechanical end stops Reset limit switches and adjust end s...