ivact IVS A Installation And Operating Manual Download Page 2

 

 

IAI5001-01 

Page 2 of 9 

07/18 

Before installing the actuator onto the valve or damper, check the following:

 

1.

 

Check the actuator nameplate for the output torque 
of  the  actuator.  The  output  torque  should  be  a 
minimum of 30% greater than the actual maximum 
requirement of the valve or damper. See Photo 1.

 

2.

 

Check to ensure that the enclosure rating is suitable 
for the area of installation.

 

3.

 

Check the wiring diagram, as per the wiring diagram 
code  on  the  nameplate,  and  confirm  that  it  meets 
the electrical requirements.

 

4.

 

Check  the  actuator  nameplate  for  correct  voltage, 
prior to wiring. See Photo 1.

 

Actuator Installation 

1.

 

The  actuators  have  been  factory  calibrated  to 
operate between 0° and 90°.

 

Most failsafe quarter-

turn products will not require recalibration of these 
settings.

 

If  any  travel  adjustment  is  necessary, 

please  refer  to  the  “Limit  Switch  Setting”  section 
below.

 

2.

 

The  actuators  are  shipped  in  the  full  CLOSE  (CW) 
position  (spring  retracted).  The  2-color  mechanical 
position indicator shows “CLOSE” (see Photo 2) and 
on the actuator base, the female drive is aligned as 
shown (see Photo 3). If the actuator is not in the full 
CLOSE  (CW)  position,  use  the  manual  override  (if 
supplied)  to  reposition  the  actuator.  See  “Manual 
Override” section below for instructions.

 

3.

 

Fully  CLOSE  the  valve  or  damper  to  which  the 
actuator is to be mounted. 

Note that the actuators 

rotate  CW  (as  viewed  from  above  the  unit)  when 
moving in the CLOSE direction.

 

4.

 

Assemble  necessary  adaption  components  and 
attach the actuator to the valve or damper.

 

Photo 2

 

Photo 3

 

Photo 1

 

Summary of Contents for IVS A

Page 1: ...Receiving Inspection Carefully inspect for shipping damage Damage to the shipping carton is usually a good indication that it has received rough handing Report all damage immediately to the freight c...

Page 2: ...ate between 0 and 90 Most failsafe quarter turn products will not require recalibration of these settings If any travel adjustment is necessary please refer to the Limit Switch Setting section below 2...

Page 3: ...Commissioning section below 12 Check below explanation of Duty Cycle The intended service should not go above the maximum duty cycle as noted on the actuator nameplate Installation Notes These actuat...

Page 4: ...ide gearbox if supplied compresses the spring as the valve is opened See Photo 4 The unit is shipped without the handwheel assembled as shown in Photo 5 Using the hardware provided thread the socket h...

Page 5: ...ctrical travel limiting device The mechanical end stop MUST always be set before the limit switch settings Ensure that the power is OFF Locate the housing cap see Photo 8 and remove the cap screws usi...

Page 6: ...he open and closed position of the valve The position is set to stop the travel of the actuator when the travel cams activate the limit switch Standard is two limit switches LS1 LS2 one for open one f...

Page 7: ...set screw on cam TC2 o Rotate cam counter clockwise to reset the switch contact o Then slowly rotate cam clockwise until a light click is heard o Securely tighten the cam and apply power to check the...

Page 8: ...oosen the set screw on cam TC4 o Rotate cam counter clockwise to reset the switch contact o Then slowly rotate cam clockwise until a light click is heard o Slowly continue to rotate in the same direct...

Page 9: ...than specified New valve may be required The voltage may be under over rated Check the supply voltage The actuator may be against one of the mechanical end stops Reset limit switches and adjust end s...

Reviews: