Page 29
Operation and maintenance
Envistar Compact
DSEC181201.00.EN
Continuous product development may give rise to specification changes without notice.
9. Reinstall the fan unit by hooking in on the key holes in the anti-vibration sup-
ports (position 4), both upper and lower, and secure the screws (position 2)
in the connection plate (position 1)
10. Check the air flows by measuring
Δ
p in the connections for flow measure-
ment. Use the unit’s air flow label and see which flow corresponds to the
measured
Δ
p.
Q=0,051* P
LUFTFLÖDE / AIRFLOW
0,30
Q (m
³/
S
)
P (Pa)
0,40
0,50
0,60
0,70
0,80
0,90 1,00
1,10
50
100
200
150
250 300
450
350 400
500
Art. NR 19121-1201
Example of air flow label
Cleaning
1. Follow item 1 under
Inspection
.
2. Wipe the fan impeller blades to remove any coatings. Use a mild, alkaline
detergent.
3. The external surfaces of the motor must be kept clean. Remove any dust,
dirt and oil. Clean with a dry cloth. In the event of stubborn dirt, use a mild
alkaline detergent. The motor is likely to overheat inside if thick layers of dirt
prevent air from entering the motor to cool the stator structure.
4. Vacuum clean inside the unit so that particles will not be blown out into the
duct system.
5. Clean the other parts in the same way as the fan impeller. Check that the
inlet cones are securely mounted.
6. Follow item 9 under
Inspection
.