Operation and Maintenance Instructions
THE NEW EcoHeater
DSEH180401.00.EN
Continuous product development may give rise to specification changes without notice.
Leakage inspection and registration
The following applies to one-piece units with 5 CO
2
e(ton) refrigerant content or
more per circuit (EcoHeater sizes 150 – 300):
•
Leakage inspection
must be carried out by a certified refrigeration techni-
cian:
– When installing/commissioning the unit
– Periodically at least once per 12 months,
i.e. no more than 12 months between inspections
– within one month of any work being performed (e.g. sealing a leak, replac-
ing a
component).
• The operator must
record
events, such as the volume and type of refrigerant
topped up, refrigerant taken into possession, results of inspections and work
done, person and company who carried out service and maintenance.
If the total refrigerant content is below 5 CO
2
e (ton) (EcoHeater sizes 060 – 100)
no periodic leak detection is needed, although an initial leak inspection should
be performed in conjunction with installation.
If the total refrigerant content of the ventilation system exceeds 14 CO
2
e(ton),
the result of the inspections (inspection report) must be sent to the regulatory
authorities and be in their possession no later than 31 March of the following
year. For a unit that will contain 14 CO
2
e(ton) or more, the intended operator
must inform the supervisory authority of the installation well in advance.
1.8 Extended warranty
In cases in which the equipment delivered falls under a 5-year warranty, in ac-
cordance with ABM 07 with supplement ABM-V 07 or in accordance with NL 09
with supplement VU13, the IV Produkt Service and Warranty Manual is supplied
with the product.
In order to lay claim to an extended warranty, a complete, documented and
signed IV Produkt Service and Warranty Manual must be presented.
1.9 Spare parts
Spare parts and accessories for this unit are ordered from your nearest IV
Produkt sales representative. When ordering, state the order number and desig-
nation.
These are stated on a data label, affixed to each component.
A separate spare parts list is supplied with the unit.
1.10 Dismantling and decommissioning
When an air handling unit is to be dismantled, separate instructions must be
followed, refer to
Dismantling and decommissioning the AHU
tion at
.