100P Enclosure 7 Adjustable Pressure Switch
Page 15
Explosion Proof/ Weather Proof Ratings:
Class I, Div 1, Groups C and D
Class II, Div 1, Groups E, F and G
Class III, Div 1
II 2 G D
Ex d II B T6 Gb
Ex tb IIIC T85 °C Db, IP65
Enclosure type 4X, 13 (NEMA)
Electrical Ratings
Form C (SPDT)
15 amp at 125, 250, or 480 VAC, 2 amp at 600VAC, 1/8 hp at
125 VAC, ¼ hp at 250 VAC, .5 amp resistive, .04 amp
inductive at 125 VDC.
Form CC (DPDT):
11 amp and ¼ hp at 125 or 250 VAC, 5 amp resistive , 3 amp
inductive at 28 VDC, .5 amp resistive at 125 VDC.
Form Z (Double Break):
15 amp at 125, 250, or 480 VAC, ¼ hp at 125 VAC, 1/2 hp at
250 VAC, 1 amp resistive, .5 amp inductive at 125 VDC.
Form C or CC with M option
1 amp at 125 VAC