background image

4

STEP 2 - Connecting the Flow Switch to Pipe

b.

Insert pipe threads into flow switch and turn 2 
or 3 times until tight.
• Place one pipe wrench on hex fitting of flow 

switch and one wrench on connecting piping.
Tighten to following torque values.
- 47 ft•lb (64 N•m) for 3/4” pipe
- 63 ft•lb (85 N•m) for 1” pipe

• Repeat to connect pipe to opposite side of 

flow switch.

a.

Apply pipe sealing compound or Teflon

®

tape to the 

pipe threads.

NOTE:

Do not apply sealant to first threads as this 

switch is grounded (earthed) via the pipe mounting.

Summary of Contents for McDonnell & Miller FS-6 Series

Page 1: ...an electrical fire or equipment damage electrical wiring insulation must have a rating of 167 F 75 C if the liquid s temperature exceeds 180 F 82 C To prevent electrocution when the electrical power i...

Page 2: ...ectronic has Type 1C action micro interruption on operation LVD 73 23 EEC EMC 89 33 EEC For applications with loads between 38mA and 3 7 Amps power factors exceeding 0 65 an anticipated system switch...

Page 3: ...1 Determine the Location of the Flow Switch 5 x D MINIMUM 5 x D MINIMUM D PIPE DIAMETER 3 4 or 1 PIPE D The flow switch should be located in a horizontal section of pipe where there is a straight hori...

Page 4: ...low switch and one wrench on connecting piping Tighten to following torque values 47 ft lb 64 N m for 3 4 pipe 63 ft lb 85 N m for 1 pipe Repeat to connect pipe to opposite side of flow switch a Apply...

Page 5: ...trical Installation To prevent electrical shock turn off the electrical power before making electrical connections To prevent an electrical fire or equipment damage electrical wiring insulation must h...

Page 6: ...itch will be used to actuate a signal alarm or other device when no flow occurs connect the wire from that device to the N C contact Connect the Hot power supply wire to C terminal Flow Opens Circuit...

Page 7: ...FLOW Adjustment Lever Screw Flow No Flow 0 12 0 06 Flow No Flow The Flow Rates Shown Are Averages May Vary 10 2 5 1 5 MAXIMUM ADJUSTMENT MINIMUM ADJUSTMENT Adjustment is necessary only if required flo...

Page 8: ...tically Solution a Adjustment screw may have been turned below original factory setpoint Verify that flow rate is high enough for flow switch to activate Measure flow rate and match with velocities sh...

Reviews: