background image

®

Series FS6
Flow Switch

Series FS-6

Series FS6-W

• Before using product, read and understand instructions.

• Save these instructions for future reference.

• All work must be performed by qualified personnel trained in the proper application,

installation, and maintenance of plumbing, steam and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.

• To prevent electrical shock, turn off the electrical power before making electrical

connections.

• To prevent an electrical fire or equipment damage, electrical wiring insulation must have a 

rating of 167˚F (75˚C) if the liquid’s temperature exceeds 180˚F (82˚C).

• To prevent electrocution, when the electrical power is connected to the flow switch, do not 

touch the terminals.

• Make sure flow switch electrical cover is secured before turning on electric power.

Failure to follow this warning could cause property damage, personal injury or death.

WARNING

CAUTION

!

WARNING

OPERATION

This control is an independently mounted water flow
sensing device that makes or breaks an electrical
circuit when flow stops or starts.

(specified models only)

McDonnell & Miller

Installation & Maintenance 

Instructions 

MM-619(C)

Summary of Contents for McDonnell & Miller FS-6 Series

Page 1: ...an electrical fire or equipment damage electrical wiring insulation must have a rating of 167 F 75 C if the liquid s temperature exceeds 180 F 82 C To prevent electrocution when the electrical power i...

Page 2: ...ectronic has Type 1C action micro interruption on operation LVD 73 23 EEC EMC 89 33 EEC For applications with loads between 38mA and 3 7 Amps power factors exceeding 0 65 an anticipated system switch...

Page 3: ...1 Determine the Location of the Flow Switch 5 x D MINIMUM 5 x D MINIMUM D PIPE DIAMETER 3 4 or 1 PIPE D The flow switch should be located in a horizontal section of pipe where there is a straight hori...

Page 4: ...low switch and one wrench on connecting piping Tighten to following torque values 47 ft lb 64 N m for 3 4 pipe 63 ft lb 85 N m for 1 pipe Repeat to connect pipe to opposite side of flow switch a Apply...

Page 5: ...trical Installation To prevent electrical shock turn off the electrical power before making electrical connections To prevent an electrical fire or equipment damage electrical wiring insulation must h...

Page 6: ...itch will be used to actuate a signal alarm or other device when no flow occurs connect the wire from that device to the N C contact Connect the Hot power supply wire to C terminal Flow Opens Circuit...

Page 7: ...FLOW Adjustment Lever Screw Flow No Flow 0 12 0 06 Flow No Flow The Flow Rates Shown Are Averages May Vary 10 2 5 1 5 MAXIMUM ADJUSTMENT MINIMUM ADJUSTMENT Adjustment is necessary only if required flo...

Page 8: ...tically Solution a Adjustment screw may have been turned below original factory setpoint Verify that flow rate is high enough for flow switch to activate Measure flow rate and match with velocities sh...