6 Troubleshooting
6.1 Troubleshooting
Symptom
Cause
Remedy
Insufficient or no dis-
charge
Speed too low due to low voltage
Verify voltage is within rated range
System head too high
Verify discharge pressure
Insufficient NPSH or submergence
Verify liquid level is above minimum required
Worn pump parts
Check parts for wear
Incorrect motor rotation
Verify rotation and swapped 2 of 3 motor leads if
necessary
Incomplete pump priming due to plug-
ged vent hole
Check vent hole
Clogged suction or discharge pipe
Clean suction area and check discharge piping for
clogs
High fluid viscosity
Check for solids settling that has increased viscosi-
ty.
Excessive current
draw
Low system head allowing pump to op-
erate at higher flow than expected
Check discharge pressure. If lower than expected,
increase with discharge valve if available
Impeller rubbing or solid stuck in pump Check that impeller turns freely. Disconnect and
lockout power. Heed all safety precautions and
warnings in this manual
Mechanical defect in motor
Repair motor at ABB/Baldor/Reliance Authorized
repair center
Specific gravity or viscosity too high
Check for solids settling that has increased viscosi-
ty.
Low voltage
Verify voltage is within rated range