TROUBLESHOOTING 

 

When performing necessary corrective action in the following operations, refer to the 

MAINTENANCE

 section for the necessary 

procedure. 
 

PROBLEM: 

The regulated pressure continues to increase after lock-up and without change in the control mechanism position. 
 

POSSIBLE CAUSE: 

The main valve seat needs replacement; follow maintenance procedure and regulator assembly.  

 
 

PROBLEM: 

Continuous leakage through the bonnet with the outlet pressure on the regulator.  
 

POSSIBLE CAUSE: 

Sensor O-ring is worn, leaking, and needs to be replaced.  
 
 

PROBLEM:

 

Regulated pressure drops off sharply when the flow is within the regulator’s capabilities. 
 

POSSIBLE CAUSE: 

Clogged inlet screen. Remove the old filter with a sharp instrument and press in a new filter using the blunt end of an instrument. 
 
 

PROBLEM:

 

Outlet Pressure will not adjust high enough. 
 

POSSIBLE CAUSE: 

Supply pressure is too low and needs to be increased.  
Maximum pressure limit (handwheel) is improperly adjusted and needs to be re-adjusted, follow maintenance procedure “setting the 
maximum output limit.” 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 
 
 

An ITT Company 

Summary of Contents for Conoflow HP400

Page 1: ... code page 3 An internal filter screen is provided in the inlet IN port only to stop random contamination resulting from installation An auxiliary filter is recommended for all but the cleanest fluid Gaseous fluid must be free of excessive moisture to prevent internal icing or condensation during operation OUTLET PRESSURE RANGES OPTION CODE RANGE J 20 2500 PSIG 0 14 17 25 MPa PORTING CONFIGURATION...

Page 2: ...m bore Other tools and maintenance aids include a vise tweezers clean lint free cloth swabs and a torque wrench CAUTION MAINTENANCE It is recommended that maintenance be performed by a person experienced in the operation and repair of high pressure regulators Maintenance of this unit is best performed by gripping a protruding end of a pipe fitting installed into the regulator body WARNING Bleed Sy...

Page 3: ... in detail the full scope of the product line In addition to the materials of construction diaphragm and elastomer selection it also provides all necessary data regarding adjustment option and range selections Control Engineering Data also provides a means of communicating by way of a code number which is fully descriptive in product selection All catalog numbers received must contain fifteen 15 c...

Page 4: ...REGULATIONS EAR THIS INFORMATION SHALL NOT BE PROVIDED TO NON US PERSONS OR TRANSFERRED BY ANY MEANS TO ANY LOCATION OUTSIDE THE UNITED STATES CONTRARY TO THE REQUIREMENTS OF THE EAR CONNECTION IDENTIFICATION AND TYPICAL GEOMETRY FIGURE 1 HP400 REGULATOR SECTIONED VIEW FIGURE 2 HP400 REGULATOR EXPLODED VIEW ...

Page 5: ... EAR THIS INFORMATION SHALL NOT BE PROVIDED TO NON US PERSONS OR TRANSFERRED BY ANY MEANS TO ANY LOCATION OUTSIDE THE UNITED STATES CONTRARY TO THE REQUIREMENTS OF THE EAR FIGURE 3 STANDARD HANDKNOB DIMENSIONAL DRAWING FIGURE 4 OPTIONAL WRENCHKNOB DIMENSIONAL DRAWING FIGURE 5 OPTIONAL T BAR HANDLE DIMENSIONAL DRAWING ...

Page 6: ...E The main valve seat needs replacement follow maintenance procedure and regulator assembly PROBLEM Continuous leakage through the bonnet with the outlet pressure on the regulator POSSIBLE CAUSE Sensor O ring is worn leaking and needs to be replaced PROBLEM Regulated pressure drops off sharply when the flow is within the regulator s capabilities POSSIBLE CAUSE Clogged inlet screen Remove the old f...

Reviews: