FIGURE 5

PROGRAMMING
RING

TIMING ARROW

ON, OFF, AUTO SWITCH

PROGRAMMING
TABS

REAL TIME
CLOCK

AQUASTAT AND TIMER INSTALLATION

1. Follow  the  installation  steps  in  both  sections  and  see

Figure 3 for wiring connections.

TIMER PROGRAMMING

1. Adjust the programming ring on the unit by turning it in the

direction of the rotation arrow until the timing arrow points
to  the  actual  time  of  day.  (This  can  also  be  accomplished
by rotating the minute hand on the real time clock, (shown
in figure 5) clockwise, until both the real time clock and the
timing arrow indicate the actual time of day.)

2. Restore  power  to  the  circulator  and  set  the  switch  on  the

timer dial to the “

I

” (ON) position.

3. Program the “ON/OFF” times by pushing the programming

tabs toward the center of the dial for “OFF” operation and
toward the outside of the programming ring for “ON” time
periods.  A  pencil,  pen  or  similar  object  may  be  used  in
making adjustments to the programming tabs.

4. Set  the  manual  switch  to  the  “TIMER” position,  which  is

centered  between  the  “

I

”  and  “O”  on  the  timer  dial,  in

order to cycle the pump according to the programming tab
settings.  The  pump  will  run  continuously  when  the  switch
is set to the “

I

” (ON) position. The “O” (OFF) position of the

switch will shut the circulator off at all times.

5. In the event of a power outage, the timer must be adjusted

for the correct time of day after power is restored.

 

3

FIGURE 3

FIGURE 4

BLACK

WHITE

BLACK

WHITE

N
L

BLACK

CAPACITOR

AQUASTAT

TIMER

POWER
LEADS

SUPPLIED BY
OTHERS

WHITE

5 4

3

2

1

Summary of Contents for Bell & Gossett Aquastat Series

Page 1: ...irculate water when the ON time conditions are met and when the water temperature is low enough to cause the aquastat to switch ON OPERATIONAL LIMITS For use on B G models NRF NBF Series PL indoor use only Power supply 115 120 VAC 60Hz 1Ø Minimum switch interval 15 minutes Run Modes ON continuous run OFF off at all times TIMER run at programmed intervals Maximum switch current 16 amps Aquastat swi...

Page 2: ...he aquastat is installed without the timer the steel cover is reassembled on the pump after the aquastat installation is complete 3 Fasten the aquastat clip to the discharge or suction pipe of the pump 4 Make the electrical connections according to the wiring diagram provided See Figure 1 5 Reassemble the conduit box cover to the conduit box while insuring that all wires are inside the box Reinsta...

Page 3: ...l to the I ON position 3 Program the ON OFF times by pushing the programming tabs toward the center of the dial for OFF operation and toward the outside of the programming ring for ON time periods A pencil pen or similar object may be used in making adjustments to the programming tabs 4 Set the manual switch to the TIMER position which is centered between the I and O on the timer dial in order to ...

Page 4: ...unded conductor To reduce the risk of electric shock connect only to a properly grounded grounding type receptacle Failure to follow these instructions could result in serious personal injury or death FIGURE 6 ITT 8200 N Austin Avenue Morton Grove IL 60053 Phone 847 966 3700 Fax 847 966 9052 www bellgossett com Copyright 2009 ITT Corporation Printed in U S A 10 09 THE ITT ENGINEERED BLOCKS SYMBOL ...

Reviews: