Operation: CP1SD/T/L Version
CENTRON® Polyphase Meter Technical Reference Guide
37
Test Mode Button
The Test Mode button is located at the 3 o'clock position under the meter cover. Pressing the
button activates Test Mode. Test Mode is indicated by the “TEST” annunciator on the lower
left of the LCD. Pressing the button a second time activates Test Alternate Mode, enabling
the user to test a different energy quantity with the IR LED. Test Alternate Mode is
indicated by the “TEST” and “ALT” annunciators on the lower left of the LCD. Pressing the
button a third time will exit Test Mode and activate the Normal display.
If the TEST button is disabled through programming, the meter will not enter Test
Mode when the button is pressed.
Factory Reset
To return the meter to its original factory settings, you must perform a factory reset. A
factory reset is also referred to as a “three button reset”.
All programming of the meter will be lost when a factory reset is performed.
All security codes are also cleared.
To perform a factory reset, do the following:
1
Activate the magnetic switch.
2
Press and hold
the Demand Rest button.
3
Press and hold
the Test Mode button.
4
While continuing to hold all buttons, cycle the power to the meter OFF, and then back
ON. You do not need to hold the buttons while turning the meter OFF, only while
turning it ON.
5
Once completed, the meter may possibly display "
3BReset
" or "
NorDisplay
" and all
segments will blink.
The original factory settings of the meter are restored.
Application of Power and Power-up
To energize all electronics, apply 120-480V (50/60 Hz) between A-phase and Neutral.
Do not power up the meter if the upper and lower housing are not
properly secured. Line-level voltages are present inside the housings.
Failure to follow this procedure could result in serious personal injury
or death.