ITR MUPASZ 710 plus User Manual Download Page 30

   

User manual   

Strona 30 z 36 

 

IU_M710P_MANUAL_05i00_ENG 

3.13.2.

 

CBCT - Circuit Breaker Control Test 

 

 Menu > Management > Diagnostics > CBCT – Circuit Breaker Control Test 

 
CBCT  -  Circuit  Breaker  Continuity  Test

  checks  the  continuity  of  the  control  lines  of  the  breaker  coils  and 

auxiliary voltage. Lack of continuity is indicated by a message on the LCD display, the LED diode and the relay 
UP output (memorized signalization). Signaling can be reset by pressing UP button on the operator panel.

 

 The CBCT can be blocked in the device settings independently for opening and closing circuits. 

 

3.13.3.

 

HVT - High Voltage Test 

 

 Menu > Management > Settings > Settings X >Autotest > HVT 

 

HVT  –  High  Voltage  Test 

  checks  the  cable  insulation 

using  external  high  voltage  generator.  It  allows  testing 
cable  insulation  and  verify  the  operation  of  the 
generator  using  an  external  test  resistor.  HVT  can  work 
in  manual  and  automatic  modes.  In  the  manual  mode, 
the  test  is  triggered  by  operator  request.  In  the 
automatic  mode,  it  is  possible  to  test  the  generator  at 
the  request  of  the  operator,  and  the  test  runs 
automatically before each closing of the circuit breaker. 

 

 

 

3.13.4.

 

PAT - Protection and Automation Test 

 

 Menu > Management > Settings > Settings X >Autotest > PAT 

 
PAT    –  Protections  and  Automation  Test 

  check 

operation of the protections and the automatic functions 
using external testers. It allows to check protections and 
automatic  functions  including  inputs  circuits  (measuring 
and  digital  inputs)  used  by  the  algorithm.  PAT  requires 
the test signal generators that are attached to the inputs 
of  the  bay  controller.  After  the  start,  test  signals  are 
attached  to  inputs  and  PAT  checks  the  response  to  the 
signals. PAT can work in manual and automatic modes. In 
the manual mode test are initiated by an operator while 
in  the  automatic  mode  tests  run  periodically  at  preset 
hours. 

 

 

 

 

 

Summary of Contents for MUPASZ 710 plus

Page 1: ...Bay control unit User manual Document version 05i00 Update 2015 01 22 energetyka itr org pl...

Page 2: ...eserve the right to modify the device Tele and Radio Research Institute ICT and Electronics Centre 03 450 Warsaw ul Ratuszowa 11 tel faks 48 22 619 73 14 e mail energetyka itr org pl www energetyka or...

Page 3: ...tection 26 3 11 2 DAR Fault recorder 26 3 11 3 CDAR Criterion recorder 27 3 11 4 PQA Power Quality Analyzer 27 3 11 5 SLOG System Log 27 3 11 6 UPS Uninterruptible Power Supply 28 3 11 7 RPS Redundant...

Page 4: ...bay controller may have up to 8 bay types profiles implemented which may be freely modified and adapted to the user s requirements Logic function simulator is included The user may also redesign impl...

Page 5: ...log outputs user commands Automatic functions AACF Automatic Active Component Forcing ACCB Automatic Connection of Capacitor Battery CBF Circuit Breaker Failure AUFLS Automatic Under Frequency Load Sh...

Page 6: ...harm Tp bay working time I cumulated current resistance Rrotor Rhvt Measurements set two current 2 I1 2 I2 2 I3 voltage 2 U1 2 U2 2 U3 2 U12 2 U32 2 U13 frequency 2 f Diagnostic SC Selfcheck voltage...

Page 7: ...lements of synoptic available switches electrical symbols lines nodes texts measurements clock states of binary inputs and outputs events messages signaling operational states Other functions 4 sets o...

Page 8: ...ics grouped into sets of set points Texts Used to preview texts predefined in the device in supported languages and to edit editable texts Available via ELF program Selected counters Used to configure...

Page 9: ...agnostic SC Self check monitoring of internal states of the device MAC Manual algorithm check simulates measurement values and allows verification of correct operation of an algorithm CBD Circuit brea...

Page 10: ...or communication with ELF software tool Fig 2 1 1 Front panel 1 Freely programmable diodes diode descriptions on graphic display 2 Colour graphic 320x240 pixels display 3 Emergency opening signalizati...

Page 11: ...e Local or Local and remote mode must be active Additionally access to the close command may be restricted for some users see Part 3 9 2 1 User Manager 2 1 2 Signal diodes In addition to graphic displ...

Page 12: ...e contains the window caption i e the name of relevant branch or window the user is watching at 2 On the right hand side of the caption icons are located which inform about alarms locks and emergency...

Page 13: ...ng id displayed in the bottom line For example in order to move from the main window to the Logging window the following path should be followed Menu Management Monitoring Logging or to use the Loggin...

Page 14: ...isplaying it as not monitored Control activates the mechanism of switch control Activation of this option marks the main switch Another switch may be selected with the keys The switches which cannot b...

Page 15: ...ing to the widow with descriptions of the other diodes 3 5 Event log Menu Event log Event log The Event log holds events generated in the device and allows their viewing Any recorded event is characte...

Page 16: ...Lock Execution of an algorithm e g protection set to lock Lock or Temporary lock selected in Options Executed Execution of an algorithm e g protection 3 6 Measurements Menu Measurements Measurements...

Page 17: ...rms Alarms MUPASZ 710 plus implements a series of switch bay protection algorithms In order to facilitate reading of operating state of algorithms the software of MUPASZ 710plus device is fitted with...

Page 18: ...roup Selection of control If in the bay operation logic scheme the control mode selection is done via binary inputs then selection of the control mode via the user interface is disabled 3 8 2 User com...

Page 19: ...he key the Control window opens In case the selected switch is not intended for control via the interface the message Lack of control is displayed If the selected operation is allowable it will be exe...

Page 20: ...e set of settings being edited Menus of all sets of settings for a given profile are identical Algorithms of protections and automatic functions control and monitoring functions and nominal values are...

Page 21: ...tarting edition of settings one should first set the nominal values Bay settings Nominals because their values may influence the way the protections and automatic functions operate and their operating...

Page 22: ...out saving changes Edition of a NUMBER parameter consists in entering the number in accordance with the format and within allowable range The name of the edited parameter is displayed in the window he...

Page 23: ...ogging in was lately used Producer and Service users have privileges allowing servicing of the devices these privileges are not granted to the operating personnel Activation of the Auto login function...

Page 24: ...al Inputs outputs In this window current states of device binary inputs and outputs are displayed High state of input output is marked with the symbol low state with the _ symbol 3 9 3 Configuration 3...

Page 25: ...ition of parameters 3 9 3 3 Date and time Menu Management Configuration Clock Menu Management Configuration Clock options After entering the Clock window in the first line current date and time is dis...

Page 26: ...ow voltage CB trip coils what ensures CB opening even when no auxiliary supply is available in the switchgear Breaking current is also monitored and in case the maximum allowable local switch breaking...

Page 27: ...al 3 11 4 PQA Power Quality Analyzer Menu Management Extensions PQA Power Quality Analyzer The application is intended for energy quality analysis in the object that is being protected according to PN...

Page 28: ...the situation The system reaches full capacity after 10 minutes of charging 3 11 7 RPS Redundant Power Supply RPS solution consists of two independent power supplies The default power supply for the...

Page 29: ...ring normal exploitation without disconnecting it from the network Basing on the acquired information the comprehensive breaker diagnostics is carried out including its wear and possible future malfun...

Page 30: ...rator using an external test resistor HVT can work in manual and automatic modes In the manual mode the test is triggered by operator request In the automatic mode it is possible to test the generator...

Page 31: ...unctions transfer inter bay lock messages synchronize internal clocks with system clock transmit content of recorders reprogramming of the device Each version of the device is accompanied by documenta...

Page 32: ...hod for communication ports of devices installed at various locations of communication network are the same as for 2 wire version Type I 4 wire Fig 4 1 3 Intermediate position of the device in 4 wire...

Page 33: ...tion of the device in 2 wire communication network Type II 2 wire Fig 4 2 2 Extreme position of the device in 2 wire communication network It is recommended that shielded twisted pair is used with cha...

Page 34: ...ing particular attention to proper matching Tx and Rx transmission directions During transportation and when cables are not connected optical sockets should be protected with sealing caps If the optic...

Page 35: ...hing It is recommended that the internal battery is replaced at least once every 10 years The battery should be replaced by service personnel as indicated by manufacturer Differences observed during c...

Page 36: ...ded by a period of residence of the product in the repair Unauthorized tampering with the product will void the warranty Warranty does not cover damage resulting from improper use of the product 5 6 S...

Reviews: