User manual
Strona 18 z 36
IU_M710P_MANUAL_05i00_ENG
3.8.
Control mode
3.8.1.
Selection of control mode
Menu > Control > Selection of control
One of four control modes may be selected in the
Selection
of control
window:
Local
– via device interface,
Remote
– via communication system,
Local and remote
– via device interface /
communication system,
Autonomous control
– control without
participation of the device (CB is controlled by external
devices).
See chapter
3.9.1.1 Edition of parameters.
Before setting the control mode one should check if the intended mode is allowed in settings. -
Menu >
Management > Settings > Settings X > Control group > Selection of control.
If in the bay operation logic scheme the control mode selection is done via binary inputs then selection
of the control mode via the user interface is disabled.
3.8.2.
User commands
Menu > Control > User commands
ELF software tool allows the user to define own
commands which activate logic functions from the
device menu level.
Commands are configured by means of ELF program, in
the tab
Logic
; configuration consists in entering the
CMD_USER block and connecting its output signal to the
block of the function it is to activate. Selecting the
command from device menu shall activate the
instruction resulting from the logic.
User commands
may be used to control the switches, cancel signaling, activation of algorithms or
execution of any user designed function present on the device logic scheme.