![Itelco-Clima CWP-CO Installation And Maintenance Manual Download Page 26](http://html1.mh-extra.com/html/itelco-clima/cwp-co/cwp-co_installation-and-maintenance-manual_2095504026.webp)
Page 25
English
Technical data
(1) With R22, on demand, for extra-European countries.
(2) Indicative value. Always refer to the value specified on the unit’s label.
CWP
15
18
21
25
30
35
Power supply
V/ph/Hz
400/3/50
Number of circuits
1
1
1
1
1
1
Number of steps
1
1
1
2
2
2
Refrigerant
Type (1)
R407C
Charge (2)
kg
4.3
12
5
8.5
9
11.2
Compressors
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Number
1
1
1
2
2
2
Start-up type
Direct
Direct
Direct
Direct
Direct
Direct
Evaporator
Type
Plate type
Number
1
1
1
1
1
1
Minimum water content
l
2.8
4.4
5.3
6.9
8.6
10.9
Condenser
Type
Plate type
Number
1
1
1
1
1
1
Minimum water content
l
2.8
4.4
5.3
6.9
8.6
10.9
Evaporator Hydraulic connections
Type
Gas threaded female type
Inlet diameter
inch
1"
1
/
2
1"
1
/
4
1"
1
/
4
2"
2"
2"
Outlet diameter
inch
1"
1
/
2
1"
1
/
4
1"
1
/
4
2"
2"
2"
Condenser Hydraulic connections
Type
Gas threaded female type
Inlet diameter
inch
1"
1
/
2
1"
1
/
4
1"
1
/
4
2"
2"
2"
Outlet diameter
inch
1"
1
/
2
1"
1
/
4
1"
1
/
4
2"
2"
2"
Weights
Shipping weights
kg
270
295
306
508
541
574
Operating weights
kg
274
290
300
500
530
560
Dimensions
Length
mm
1100
1100
1100
1700
1700
1700
Height
mm
1100
1100
1100
1200
1200
1200
Width
mm
850
850
850
984
984
984
Manuale CWP 4.11.2005 11:56 Pagina 25