ITE - Sint-Niklaas - Belgium - Fax : +32 3 766 10 67 - [email protected]
NOTE:
To avoid damaging the wrench; never turn the scale below 10 Nm.
For other torque settings than shown in the above table, adjust the scale to
the nearest value and increase or decrease the torque by turning the handle,
knowing that each increment on the handle represents 1 Nm.
5. Lock the handle by turning the locking pin clockwise and firmly locking it.
6. When using the wrench, and the desired torque is reached, the user will feel a little jolt
and a decrease of effort.
ATTENTION :
To avoid damaging the wrench, stop applying force once you have reached the desired
torque.
To not compromise the precision of the wrench; after use, always re-set the wrench to
its smallest value.
When the wrench hasn’t been used for a long time, firstly use the wrench and jolt it a
few times in its smallest setting, to insure correct internal lubrication.
The side of the wrench-head that shows the size has to be on the same side as the
direction arrow on the wrench.
Value to set
Type of refrigerant
Nut
Wrench-head
180 kg x cm (18 Nm)
Tradi R410a
1/4
17
420 kg x cm (42 Nm)
Tradi R410a
3/8
22
550 kg x cm (55 Nm)
Traditional
1/2
24
550 kg x cm (55 Nm)
R410a
1/2
26
650 kg x cm (65 Nm)
Traditional
5/8
27
650 kg x cm (65 Nm)
R410a
5/8
29