background image

ClayPower Online UPS 

1. Important Safety Warning

Please comply with all warnings and operating instructions in this manual strictly. Save this 

manual properly and read carefully the following instructions before installing the unit. Do not 

operate  this  unit  before  reading  through  all  safety  information  and  operating  instructions 

carefully 

1.1. Transportation 

Please transport the UPS system only in the original package to protect against shock

and impact.

1. 2.  Preparation 

Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please

allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or near
heater.

Do not block ventilation holes in the UPS housing.

1.3. Installation 

Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.

The UPS can be operated by any individuals with no previous experience.

The UPS can be operated in TN&TT power distribution.

Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
Please use only UL-tested, UL-marked mains cable (e.g. the mains cable of your

computer) to connect the UPS system to the building wiring outlet (shockproof
outlet).

Please use only UL-tested, UL-marked power cables to connect the loads to the UPS
system.

When installing the equipment, it should ensure that the sum of the leakage current

of the UPS and the connected devices does not exceed 3.5mA.

1.4. Operation 

Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective
earth of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is not

connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to

disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.

The EPO, RS-232 and USB circuits are an IEC 60950 safety extra low voltage (SELV)

circuit. This circuit must be separated from any hazardous voltage circuits by

reinforced insulation.

Summary of Contents for ClayPower

Page 1: ...ClayPower Rack Tower On Line UPS USER MANUAL...

Page 2: ...rating principle 4 2 3 Installing the UPS 4 2 4 Setup the UPS 6 2 5 Battery replacement 8 2 6 Battery kit assembly optional 9 3 Operations 11 3 1 Button operation 11 3 2 LCD panel 11 3 3 Audible Alarm...

Page 3: ...erated by any individuals with no previous experience The UPS can be operated in TN TT power distribution Connect the UPS system only to an earthed shockproof outlet which must be easily accessible an...

Page 4: ...tion risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the ground Before touching please verify that no v...

Page 5: ...rent types of online UPS standard and long run models Please refer to the following model table Model No Type Model No Type CP 900W 2U Standard Model CP 900W L 2U Long Run time Model CP 1350W 2U CP 13...

Page 6: ...he operating principle of the UPS is as shown below The UPS is composed of mains input TVSS and EMI RFI filters rectifier PFC inverter battery charger DC to DC converter battery dynamic bypass and UPS...

Page 7: ...hassis Please choose proper installation to position this UPS Install the UPS and external battery Install the UPS and external battery NOTE When installing the UPS or battery pack with feet please ke...

Page 8: ...tions Communication port USB port RS 232 port Intelligent slot To allow for unattended UPS shutdown start up and status monitoring connect the communication cable one end to the USB RS 232 port and th...

Page 9: ...during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 8 Installing software For optimal computer system protection install U...

Page 10: ...ons and notes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Ste p 3 Remove front panel Disconnect battery wires Pull out the ba...

Page 11: ...ep 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 3 battery kit Step 1 Remove adhesive tapes...

Page 12: ...hells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below c...

Page 13: ...bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to...

Page 14: ...voltage V voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuited UPS status Indicates...

Page 15: ...ding 3 4 LCD display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape RAC Rack display TOE Tower display B L Low Battery O L Overload N C Battery is not connected...

Page 16: ...odels you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage is 120Va...

Page 17: ...erface Setting ENA Advanced ECO mode enable DIS Advanced ECO mode disable 06 Bypass mode enable disable Interface Setting ENA Bypass mode enable DIS Bypass mode disable 07 Programmable outlets enable...

Page 18: ...may choose the following Acceptable input voltage range 110 300 alternating flashing acceptable input voltage range is from 110V to 300V 160 260 alternating flashing acceptable input voltage range is...

Page 19: ...ut voltage is within setting range 3 V o max UPS will bypass voltage to output for energy saving PFC and INVERTER are off at this mode Frequency Converter mode When input frequency is within 40 Hz to...

Page 20: ...27 x Bus unbalance 04 x Battery voltage too low 28 Inverter soft start fail 11 x Over temperature 41 x High Inverter voltage 12 x Overload 43 3 8 Warning indicator Warning Icon flashing Code Alarm Lo...

Page 21: ...n and flashing on LCD display and alarm is sounding every second The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the i...

Page 22: ...output wiring and if connected devices are in short circuit status Fault code is shown as 01 02 03 04 11 12 13 and 41 on LCD display and alarm is continuously sounding A UPS internal fault has occurr...

Page 23: ...your dealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage T...

Page 24: ...h Depending on application 12V 9Ah Depending on application 12V 9Ah Depending on application Quantity 2 3 4 6 Typical Recharge Time 4 hours recover to 90 capacity for standard model only Charging Curr...

Page 25: ...Blank Page...

Reviews: