Generator Voltage Lower
Limit:
If the voltage of the generator output falls below generator
voltage lower limit a shutdown is initiated. The module will
indicate voltage failure.
P16
Generator Fault Control
Delay:
If the generator voltage or frequency is out of acceptable
limits, the module will wait during the generator fault control
delay timer before indicating any alarm condition. This
parameter is useful during instant load changing.
P17
Mains Voltage Lower Limit:
If the voltage of the mains falls below mains voltage lower
limit the module will indicate mains failure
.
P18
Mains Voltage Acceptance
Limit:
If the voltage of the mains exceeds mains voltage acceptance
limit the module will accept the mains normal.
P19
Mains Voltage Upper Limit
If the voltage of the mains exceeds mains voltage upper limit
the module will indicate mains failure.
P20
Generator Frequency For
Crank Disconnection:
If the frequency of the generator output exceeds this limit,
the crank is disconnected.
P21
Configurable Output:
Auxiliary output function can be configured as one of the
following:
a-Prh(preheat):
Auxiliary output relay is energized and
outputs battery positive voltage to provide preheat function
during start delay timer.
b-Opt(engine running):
Auxiliary output relay is energized
and outputs battery positive voltage to indicate engine
running.
c-Auto (automatic mode):
Auxiliary output relay is
energized and outputs battery positive voltage to indicate
automatic mode.
P22
Configurable Input:
Auxiliary input function can be configured as one of the
following:
a-NC(Normally closed):
Auxiliary input is configured as
shutdown failure by disconnecting the input from the battery
negative voltage. It is enable during engine running.
b-NO(Normally Open):
Auxiliary input is configured as
shutdown failure by connecting the input to the battery
negative voltage. It is enable during engine running
c-dsb(Remote Disable):
The module is prevented to operate
by connecting the input to the battery negative voltage. This
function is enabled in auto mode.
d-220(Mains Simulate):
The mains voltage is accepted
normal by connecting the input to the battery negative
voltage. This function is enabled in auto mode.
P23
Solenoid selection:
a-Ful(Fuel solenoid):
Fuel solenoid is energized while
cranking.
b-Stp(Stop solenoid):
Fuel solenoid is de-energized while
cranking.It is energized while engine is stopping.
P24
Frequency selection:
a-50Hz:
Mains frequency is 50Hz.
b-60Hz:
Mains frequency is 60Hz.
P25
Charge failure selection:
a-y(Yes):
Charge signal is activated. It is used while engine
is cranking and stopping. While engine is running, if the
charge signal isn’t monitored, the module will indicate a
failure.
b-n(No):
This parameter is selected if the charge signal isn’t
used.