11
to start have been completed, the module will indicate start
fail.
P02
Starting Attempt Duration
(Crank Timer):
The engine is cranked for the duration of the starting attempt
duration.
P03
Waiting Duration Between
Starting Attempts(Crank
Rest Timer):
If the engine not fire on the first attempt and the crank timer
expires, the module will rest the starter for the duration of
the crank rest timer.
P04
Stopping Duration:
Once the cooling timer has expired the module will de-
energize the
fuel solenoid
and the engine will be brought to
rest after the stooping duration timer expires.
P05
Maximum Stopping
Duration:
If the engine is still running when the stopping duration
timer expires, the module will indicate fail to start alarm
after maximum stopping timer expires. By pressing the off
button, the timer is initiated again.
P06
Engine Cooling Duration:
After the module de-energize the generator contactor output,
the module will then initiate its cooling timer. This allows
the engine to run off load to ensure that it has adequately
cooled before being brought to a standstill.
P07
Mains Transition Delay:
When the mains returns within the limits, the module will
first initiate mains transition delay timer to ensure that it is
safe to stop the generator. If the mains voltage has no failure
after this timer expires, the module will initiate mains
contactor delay timer.
P08
Generator Contactor Delay:
After the starter motor is detected starting, the generator
contactor delay timer is activated
.
After this timer expires,
the module will energize the generator contactor if there is
no failure with the generator signals.
This parameter must be adjusted bigger than P11
parameter.
P09
Mains Contactor Delay:
If the mains voltage has no failure after the mains transition
delay timer expires, the module will initiate mains contactor
delay timer. When the timer expires, the module will
energize the mains contactor output...
P10
Oil Pressure Control Delay:
The module will indicate start failure, if the oil pressure is
still high after expiring the oil pressure control delay timer.
P11
Fault Control Delay:
If the engine start is successful, the fault control delay timer
is activated. This timer allows Oil Pressure, High Engine
Temperature, Under speed, Under volts, Charge Fail and any
delayed auxiliary fault inputs to stabilize without triggering
the fault. Once the engine is running and the fault control
delay timer has expired, full fault protection is made
available.
P12
Generator Frequency Upper
Limit:
If the frequency of the generator output exceeds generator
frequency upper limit a shutdown is initiated. The module
will indicate speed failure.
P13
Generator Frequency Lower
Limit:
If the frequency of the generator output falls below generator
frequency lower limit a shutdown is initiated. The module
will indicate speed failure.
P14
Generator Voltage Upper
Limit:
If the voltage of the generator output exceeds generator
voltage upper limit a shutdown is initiated. The module will
indicate voltage failure