The 

ASU

 processor monitors the supply voltage.   When the voltage rises above 13.2 

(26.4) volts it will start the compressor and after a short delay gradually increase the 
speed of the compressor and cooling fan.   The indicator LED will shift from yellow to 
red.  This operating condition is maintained until the holding plate is completely frozen 
at approximately -14°C (7°F).  This can take between 45 minutes and 2 hours depend-
ing on the model, ambient temperature and box size.    
 
As long as the 

ASU

 processor senses surplus power the holding plate is maintained in 

the frozen condition.  If the holding plate temperature rises to -10°C (14°F), the com-
pressor re-starts and the red LED comes on again. 
 
When the supply voltage falls below 12.7 (25.4) volt, the refrigeration energy stored in 
the holding plate will maintain the box temperature for many hours (up to 12 hours de-
pending on the box size, ambient temperature  and insulation).   
 
When all the thermal energy stored in the holding plate is used and the plate tempera-
ture rises to -1°C (30°F) the ASU system will start the compressor at a low speed to 
bring the plate temperature down 6°C (21°F).  This will maintain a very stable box tem-
perature using the minimum amount of battery power.   

 

“MAN.TEMP” position: 

 
This position can be used when shore-power is connected and energy saving is not re-
quired or whenever a higher or lower refrigerator temperature is desired.  The ASU 
program is stopped and the temperature is regulated by means of the temperature 
knob on the control panel.  Turn the control clockwise for a colder temperature setting.   
The “A” (Accumulation) position approximates the freezing point of the holding plate. 
 
In the ”MAN.TEMP” position, the compressor runs at a low speed to maintain the set 
temperature. If the difference between the set and actual temperature is greater than 
6°C, the compressor will automatically speed up for faster cooling.  As soon as the 
temperature comes down the compressor speed will be reduced for the lowest power 
consumption and quietest operation. 

 

9.2.3   INDICATOR LIGHTS 

Green:

 Power and system on, compressor not running. Set temperature reached. 

 

Green + Yellow

:  Compressor running at low speed in Normal Auto mode. 

 

Green + Red

: Compressor running at high speed in the Normal/Auto mode. 

 

Green +  Red:

 Compressor running in MAN.TEMP mode.  

 

Flashing Yellow  and/or Red:

   Error signal. See Troubleshooting Guide. 

 
Automatic Defrosting will take place automatically every tenth day of operation. 

Summary of Contents for Cruise Line

Page 1: ...Cruise Line Marine Refrigerators INSTALLATION AND OPERATING INSTRUCTIONS PRODUCED BY GREAT WATER INC BRUNSWICK MAINE WWW GREAT WATER COM 207 729 8500 TEL 517 813 6509 FAX INFO GREAT WATER COM...

Page 2: ...g the Door 6 General Maintenance 6 1 Defrosting 6 2 Cleaning 6 3 Storage 7 Cruise Models with Traditional Thermostats 7 1 Electrical Connections 7 2 Operation 7 2 1 Start Up 7 2 2 Protection System 8...

Page 3: ...contact a certified technician All Cruise refrigerators s use environmentally safe R 134a refrigerant with 0 Ozone depletion potential R 134 is non toxic in the unlikely event that it is released from...

Page 4: ...ource while making these connec tions 3 Boat s Electrical System A refrigeration system when properly installed and operating efficiently will still be a major consumer of electrical power It is impor...

Page 5: ...e lower edge of the door 5 Re hanging the Door All Cruise refrigerators doors are hung with the hinges on the right hand side of the box To re hang the door with the hinges on the left follow these st...

Page 6: ...ning The best time to clean the refrigerator is after defrosting Wipe the inside clean using soap and water or a non abrasive cleaner If you notice your refrigerator running longer than normal it may...

Page 7: ...emperature setting with the lowest temperature at the extreme clockwise position A good initial setting is mid range 7 2 2 Protection System The compressor is equipped with an electronic protection sy...

Page 8: ...heck the thermostat If the compressor still doesn t start this indicates a fault in the electronic unit or compressor Contact an authorized service agent Compressor starts but doesn t cool refrigerato...

Page 9: ...is managed to consume a minimum of battery power In the MAN TEMP position The temperature can be manually adjusted In the center position the unit is switched off 9 2 2 Operation NORMALAUTO position T...

Page 10: ...21 F This will maintain a very stable box tem perature using the minimum amount of battery power MAN TEMP position This position can be used when shore power is connected and energy saving is not re...

Page 11: ...insulation Re insulate Fan not running or too warm in compressor compartment Repair fan or ventilate the space us ing air hose kit part 10 10013 Too much gas in system frost on pipe Refrigeration spe...

Page 12: ...is absorbed from the box to boil the refrigerant The main difference is the refrigerant boils at a much lower temperature than water The boiled refrigerant gas is pumped out of the evaporator by the...

Reviews: