How to Install the ISONAS PureIP Reader-controller 

 

 

A standard CAT5/6 cable is then run between the PoE source (Injector or switch) and the Pure IP 
Reader-Controller which will be located right next to the door. The CAT5/6 cable can be up to 100 
Meters (328 feet) long, including all patch cables and patch panels. 

 
 
 
 

Supplying 12 VDC to Door Components from the PoE powered Pure IP Reader-Controller 

 

When the Pure IP Reader-Controller is powered by PoE, the reader can supply 0.6 amps @12 VDC 
power for external components.  This DC power is available via two pigtail wires. 

 

The Red pigtail wire is typically used to control the door’s lock. The Red wire’s 12VDC output will be 
activated /deactivated when the reader is operating the door’s lock. This connection has a built-in 
current limiting feature, to prevent the lock from consuming too much electrical power. 

 

The Orange pigtail wire provides a source of continuously-available 12 VDC power. You might use 
this 12VDC source to power a PIR Motion Detector located at the door location. 

 

PoE Power Budget Calculations 

 

When planning an installation using PoE, you need to validate that the PoE source (PoE Injector or 
PoE equipped Network Switch) supplying the PoE power is sized properly for all the attached PoE 
devices. To do this, you total up the power draw (in watts) of the PoE connections, and compare 
that total power draw to the rated capacity of the PoE source. 

 

Below is a chart of expected PoE power draws of the ISONAS Reader-controllers. 

 

 

Door Location Configuration 

 

PoE Power Requirement ** 
(Watts) 

 

Pure IP Reader-Controller 

 

2.3 Watts 

Pure IP Reader-Controller with 
Electronic Lock (300 mA @ 12V) 

 

6.2 Watts 

Pure IP Reader-Controller with 
Electronic Lock (600 mA @ 12V) 

 

10.4 Watts 

 

*** Ethernet cabling power losses not included. Losses range from being negligible for short 
Cat5/6 cables,  up to about 16% for 100 meter Cat5/6 cables. 

 

To meet the Pure IP Reader-Controller’s variable PoE power requirements, the Pure IP Reader- 
Controller will classify itself with the PoE source as a “Class 0” PoE device. The power usage of a 
Class 0 device can range between 0.4 to 13.0 watts at the device (up to 15.4 watts from the PoE 
source). 

Summary of Contents for OCZRC-04M

Page 1: ...How to Install an ISONAS Pure IP Reader Controller Reader Controller Copyright 2016 ISONAS Inc All rights reserved...

Page 2: ...e equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures 1 Reorient or relocate the receiving antenna 2 Increase the separation between...

Page 3: ...G THE DOORS 16 2 2 1 READER CONTROLLER CONTROL LEADS DESCRIPTION 17 2 2 2 LOCK WIRING BASIC 18 2 2 3 WIRING THE REX AUX INPUT 20 2 2 5 WIRING THE DOOR SENSE 21 2 2 7 LOCK WIRING EXTERIOR DOOR KIT 22 2...

Page 4: ...cument Version Date of Revision Revision Author Description 11 03 2016 1 00 Shirl Jones Initial Release 12 14 2016 1 01 Shirl Jones General Updates 12 20 2016 1 02 Shirl Jones Updated Cabling Guidelin...

Page 5: ...control system The Host access control system typically is one of the following PureAccess Cloud PureAccess Manager or a 3rd party ACS software package 1 5 The Pure IP Reader Controller reader compli...

Page 6: ...d 250msec Prox Exciter Field Frequency Proximity 125khz Multi Tech 13 56 MHz Modulation Schemes Proximity FSK Multi Tech ISO 14443 type A and type B Communication Interface TCP IP Over Ethernet 10 Mbp...

Page 7: ...s 4 In humid environments it is recommended that a drip loop be formed in the Pure IP Reader Controller s cables before the cables enter the reader controller 5 The reader controller should be protect...

Page 8: ...8 How to Install the ISONAS PureIP Reader controller Figure 2 Pure IP Reader Controller Mullion Mounting Diagram Figure 1 Pure IP Reader Controller Wallplate Mounting Diagram...

Page 9: ...rk configuration An installer s Tool Kit should include the following 1 A copy of the Pure IP Reader Controller Installation and Wiring Guide 2 A Volt Ohm Meter 3 Pin in Torx Screwdriver o T 8 Tamper...

Page 10: ...LED does not turn AMBER then the reset did not occur Reset Configuration Press and hold the Reset button approx 10 seconds until the RC04 s Main Status LED turns AMBER Selected reader controller confi...

Page 11: ...he Power Over Ethernet PoE option PoE allows one cable to supply data and power to the Reader controller which in turn can then supply 12VDC to the door s Electronic lock The obvious savings here is t...

Page 12: ...r a PIR Motion Detector located at the door location PoE Power Budget Calculations When planning an installation using PoE you need to validate that the PoE source PoE Injector or PoE equipped Network...

Page 13: ...wered via PoE on cable runs up to 100 meters long the standard Ethernet cable limit For RC04 locations that have longer cable runs 50 meters extra care should be given to the planning and installation...

Page 14: ...Limiting Factor Topology Diagram PoE 802 3af 0 60 amps 12VDC Pure IP Reader Controller Pure IP Reader Controller s available PoE Output A PoE 802 3af 0 55 amps 12VDC Pure IP Reader Controller EDK Pure...

Page 15: ...15 How to Install the ISONAS PureIP Reader controller Power Options Figure 4...

Page 16: ...t power to every Reader controller the next step is to connect the wiring at each door Wiring a door may involve connecting An electronic door latch A request to exit REX like REX Button Motion Detect...

Page 17: ...tallations do not require the use of all the leads The typical usage of each available lead is shown in Figure 6 Figure 6 One of the wires is for a door sense switch Another is for a REX Request for E...

Page 18: ...ock first install the lock hardware according to the manufacturer s instructions Examine the lock to determine whether applying power will lock or unlock the door Fail Safe Applying power locks the do...

Page 19: ...g used to supply the lock s power 1 Connect the Red wire on the ISONAS Reader controller to the positive lead of the electric lock See Figure 7 2 Connect the negative lead of the lock to the black wir...

Page 20: ...larm When pressed this button tells the ISONAS Reader controller that that someone wishes to pass through the door The latch releases and or the door open alarm is suppressed The reader could be confi...

Page 21: ...trol system can create alarms based on the door s state This wiring task is similar to wiring the REX AUX input First connect one terminal of the door sensor to the Reader s blue wire Then connect the...

Page 22: ...ck and the EDK with the Reader controller s PoE power See Figure 10 Figure 10 Label Reader Side Connection Label Lock Side Connection A Pigtail s Orange wire 12 V Input Power 1 12V Output Power B Pigt...

Page 23: ...gure 11 Figure 11 Label Reader Side Connection Label Lock Side Connection A Pigtail s Orange wire 12 V Input Power 1 Not Used Factory installed Jumper removed B Pigtail s Black wire Ground 2 Not Used...

Page 24: ...ader Controller Locked Pure IP Reader Controller Unlocked Lock State when Pure IP Reader Controller is unlocked Description or Item to Check Off Green Normal Operation Flash Amber Flash Amber No Opera...

Page 25: ...oor sense switch Use the following steps to cause the outside Reader to activate the REX input on the Inside Reader Two Readers One Lock Wiring Steps See Figure 12 1 Wire the Inside reader normally 2...

Page 26: ...r Controller is supplied with a diode assembly which simplifies the installation process A standard diode from any electronic supply store can also be used Always check that the diode is correctly rat...

Page 27: ...27 How to Install the ISONAS PureIP Reader controller 2 3 CONFIGUATION EXAMPLES 2 3 1 PoE ELECTRIC STRIKE Figure 14...

Page 28: ...28 How to Install the ISONAS PureIP Reader controller 2 3 2 PoE MAGNETIC LOCK EDK PIR Figure 15...

Page 29: ...29 How to Install the ISONAS PureIP Reader controller 2 3 3 DUAL POWER SOURCES Figure 16...

Page 30: ...nimal network configuration to function ISONAS provides a cloud instance of the PureAccess software The readers are configured to automatically connect to hosted PureAccess software Addressing The rec...

Page 31: ...d subnet The POE switch should have enough power to run all ports and account for in rush IE A switch restart which would cause all readers to restart Pure IP Reader Controllers to PureAccess Manager...

Page 32: ...PureIP Reader controller For more information Web www isonas com E mail sales isonas com Tel 800 581 0083 toll free or 303 567 6516 CO Fax 303 567 6991 ISONAS Headquarters 4750 Walnut Street Suite 11...

Reviews: