Manufacturer of Quality Air Conditioning and Heating Products • www.islandaire.com • sales@islandaire.com • (800)-886-2759
20
Wall Sleeve Installation Instructions (
cont.
)
Panel/Curtain/Window Wall Application
Clearances and projections
The wall sleeve will need to be installed so that the sleeve
projects into the room a minimum of 1.25 inches and a
maximum of 11.5 inches.
The wall sleeve will need to be installed so that the sleeve
projects beyond the exterior wall a minimum of 0.25
inches.
When installed in the appropriate wall sleeve, this appli-
ance has zero clearance to combustible construction.
The minimum required clearance distance between the
wall sleeve and finished floor is 3.0 inches. Wall sleeve
installations that project into the room 4.5” or more
require the use of Leveling Legs or other means of sup-
porting the wall sleeve.
Window/panel Wall Installation
For installations in windows and/or curtain or panel
walls of 2”, it is suggested that a subbase or leveling legs
kit be installed under wall sleeve.
To attach wall sleeve to the inside wall, field supplied wall
sleeve angles 1” x 1” x .065/.055 are to be used on top and
sides of wall sleeve.
Seal around the outside portion of the wall sleeve using
weatherproof caulking to form a seal against rain, snow,
and air leakage.
1/2” MAX. LONG SCREWS FOR SECURING ANGLES
TO TOP AND SIDES OF SLEEVE
WALL SLEEVE
CABINET
FRONT
SURFACE OF FINISHED
FLOOR OR CARPET
WINDOW OR WALL
CAULK ALL AROUND
WALL SLEEVE
REAR GRILLE (NOT SHOWN)
WALL SLEEVE ANGLES AND SCREWS (BY
INSTALLER)
DO NOT PUT HOLES THROUGH
BOTTOM OF WALL SLEEVE
1/4” SLOPE DOWN TO
THE OUTSIDE
1/4” MIN. PROJECTION BEYOND
EXTERIOR WALL
Front View
Make sure wall sleeve is level side-to-side
FASTEN SLEEVE
TO FRAMING WITH
WOOD SCREWS AT
SIDES & TOP
DO NOT DRILL OR ATTACH SCREWS TO
BOTTOM OF SLEEVE
Side View
INSIDE WALL
MAKE SURE WALL SLEEVE
SLOPES TO THE OUTSIDE BY
1/4 BUBBLE SHOWN ON LEVEL
3” MIN.
SUBBASE
Figure 8
Panel/Curtain/Window Wall Sleeve Installation (with Standard Islandaire Louver)