38
E
LECTROMAGNETIC
C
OMPATIBILITY
(EMC) T
ESTS
C
HAPTER
11
COMPLIANCE SPECIFICATIONS
Electrostatic Discharges
IEC 61850-3 clause 6.7.3
IEC 61000-4-2
IEEE 1613 clause 8
IEEE 1613.1 clause 8
8 kV contact, 15 kV air
Radiated Radio Frequency
Magnetic Field
IEC 61850-3 clause 6.7.3
IEC 61000-4-3
IEEE 1613 clause 7
IEEE 1613.1 clause 7
20 V/m
Fast Transient/Burst
IEC 61850-3 clause 6.7.3
IEC 61000-4-4
IEEE 1613 clause 6
IEEE 1613.1 clause 5
4 kV
Surge
IEC 61850-3 clause 6.7.3
IEC 61000-4-5
IEC 1613.1 clause 6
Power Ports: 4 kV LE, 2 kV LL
Signal Ports: 2 KV LE, 1 KV LL
Conducted Disturbance Induced
by RF Fields
IEC 61850-3 clause 6.7.3
IEC 61000-4-6
IEEE 1613.1 clause 9
0.15-80 MHz at 10 V
27, 68 MHz at 10 V
Main Frequency Voltage,
Common-mode Disturbances
IEC 61850-3 clause 6.7.3
IEC 61000-4-16
IEEE 1613.1 clause 12
30 V; cont. 300V; 1 s
Power Frequency Magnetic Field
IEC 61850-3 clause 6.7.3
IEC 61000-4-8
IEEE 1613.1 clause 10
100 A/m cont.;
1000 A/m 3 s
D.C. Voltage Dips
IEC 61850-3 clause 6.7.3
IEC 61000-4-29
60%; 0.1 s
30%; 0.1 s
A.C. Voltage Dips
IEC 61850-3 clause 6.7.3
IEC 61000-4-11
60%; 50 c
30%; 1c
D.C. Voltage Interruptions
IEC 61850-3 clause 6.7.3
IEC 61000-4-29
100%; 0.05 s
A.C. Voltage Interruptions
IEC 61850-3 clause 6.7.3
IEC 61000-4-11
100%; 5/50 c
D.C. Ripple
IEC 61850-3 clause 6.7.3
IEC 61000-4-17
IEEE 1613 clause 4.2
10% Ur_dc
5% content (different
calculation method)
Damped Oscillatory Magnetic
Field
IEEE 1613.1 clause 11
IEC 61000-4-10
100 A/m (peak)
Description
Specification
Level