background image

3020-dda.ib.rev0.doc 

Page 9 of 17

 09/03/2006

 

Handshake operation: 

 

Purpose: 

Handshake interconnection is required when two circuits are to be operated in 1:1 protection switching mode to 
provide a continuous signal output in the event of failure of the primary signal path. 

 

Priority logic: 

For this mode to be employed it is necessary to provide two programme feeds which are designated as the 

Main

 and 

Standby

 paths. 

The priority switching in normal mode follows non-reverting logic, which dictates: 

In the event of failure of main then standby DDA will assume control and become 

Main

 causing the failed 

path DDA to become 

Standby

This implies that when the failed path is restored that it will remain as 

Standby

 and not become 

Main

 unless either a 

failure of 

Main

 occurs or a manual changeover is requested. 

 

Changeover logic: 

A changeover to the companion module will occur under any of the following conditions: 

Loss of input signal 
AIS detection alarm (provided AIS is not disabled by link LK 3) 
Loss of power 

In all of the above cases switching will only occur if: 

the companion module is able to provide an output free of the same defects AND 
the changeover inhibit switch is not activated on either module. 

 

Connections: 

Handshake interconnection should only be made using either the ZDA-3021RH handshake double rear assembly. 
This rear assembly makes all the necessary connections for both logic and data signals when two DDA-3020’s are 
inserted side by side in a 3 RU frame. Individual alarm outputs are provided for each module. 

 

Logic connections: 

All required logic connections are made by tracks on the double width PCB. Automatic operation is immediately 
initiated when two modules are plugged into this type of rear assembly. 
 
No external connections are required, but external alarm connections are available from each module for use if 
desired. Additionally, each module has a connection for an external 

Make Main

 control for remote DA selection. 

 

Handshake mode detection: 

Two data lines are present on the handshake connector to indicate to each module that it is to operate in handshake 
mode.  
 

Power on reset. 

When power is applied to the pair the 

power on reset

 signal will attempt to reset both modules. However, as only 

one module can be 

Main

, the logic processor checks for handshake operation and if detected then the module, which 

was last enabled as 

Main

 will take control as 

Main

 and the other module will be forced to act as 

Reserve

 
This memory capability is due to the latching nature of the RL1 relay, which will cause the 

Main

 and 

Reserve

 paths 

to be maintained even in the absence of power. 
 
The only exception to this rule is when power is applied to a pair for the first time that they are coupled in 
handshake mode. In this special case both modules will initially have their K 3 relays in the active path condition 
and so both will attempt to become 

Main

. As the P.O.R. signal for each module will be slightly different for any two 

modules, one will reach its operating mode first and will force the other module to immediately change to become 

Reserve. 

 
As the selection of which module becomes 

Main

 is cannot be determined before installation it may be necessary to 

force the desired module to become main by pressing the 

Change Request

 button on the front panel of the desired 

module. The 

Main

 module will be indicated by the 

In Service

 LED, on the front panel, lighting. 

 

Automatic changeover: 

An automatic changeover is initiated whenever the power fails on 

Main

 and not on 

Reserve

 or when a general alarm 

is initiated on 

Main

 (indicating either loss of input signal or AIS indication if the AIS is enabled) and the 

Change

 

Inhibit

 switch is not active on either module. 

 

Manual changeover: 

A manual changeover is initiated by pressing the 

Change Request

 button on the front of the module that is required 

to become 

Main

The mechanism of the change is similar to the automatic changeover described above except that it is initiated by 
the module requesting that it become 

Main

IRT 

Communications 

www.irtcommunications.com

Summary of Contents for DDA-3020

Page 1: ...ustralia IRT can be found on the Internet at http www irtelectronics com I R T Electronics Pty Ltd A B N 35 000 832 575 26 Hotham Parade ARTARMON N S W 2064 AUSTRALIA National Phone 02 9439 3744 Fax 02 9439 7439 International 61 2 9439 3744 61 2 9439 7439 Email sales irtelectronics com Web www irtelectronics com I R T C o m m u n i c a t i o n s w w w i r t c o m m u n i c a t i o n s c o m ...

Page 2: ...n 17 This instruction book applies to units later than S N 0402001 Operational Safety WARNING Operation of electronic equipment involves the use of voltages and currents that may be dangerous to human life Note that under certain conditions dangerous potentials may exist in some circuits when power controls are in the OFF position Maintenance personnel should observe all safety regulations Do not ...

Page 3: ... in pairs for redundancy For this configuration the ZDA 3021RH double width rear assembly is needed to link the logic sections of two modules When used as a line equaliser or distribution amplifier the DDA may be housed in any of IRT s standard Eurocard frames When used in pairs for handshake operation only 3 RU chassis types may be used so that the double width rear assembly may be used The DDA 3...

Page 4: ... DDA SIGNAL PROCESSING JP1 2 JP1 1 JP3 T1 JP2 2 JP2 1 JP3 T2 JP2 3 CHANGE REQUEST JP1 3 O P 1 SK1 O P 4 SK9 O P 3 SK6 O P 5 SK7 GND JP2 4 GND JP1 4 Output Driver FPGA STM1 Generator Change over logic AIS Detector INPUT SK2 RL4 OUTPUTS SK4 Cable EQ PLL MON SK1 Block diagram DDA 3020 Signal path SK6 SK7 Output Driver Output Driver Output Driver Output Driver SK3 RL4 O P 3 O P 4 O P 2 O P 1 RL1 Gener...

Page 5: ...power has failed General alarm Contact closure to ground if a Data Loss is detected OR b AIS is detected AND the AIS disable link LK 3 is not installed AIS detection is defined as a series of all 1 s in the payload of a frame Data Loss is defined as less than 120 data 1 s in 512 G 703 data rate clock periods Connectors Data BNC Alarm Krone LSA plus Indicators DC power Data loss AIS detect Module i...

Page 6: ...l of the above cases switching will only occur if companion module is able to provide an output free of the same defects and changeover inhibit switch is not activated on either module Priority logic The priority switching in normal mode follows non reverting logic which dictates In the event of failure of main then standby DDA will assume control and become Main causing the failed path DDA to bec...

Page 7: ...for successive binary 1s An example is given in Figure A 1 NOTE 1 For binary 0 there is always a positive transition at the midpoint of the binary unit time interval NOTE 2 For binary 1 a there is a positive transition at the start of the binary unit time interval if in the preceding time interval the level was A1 b there is a negative transition at the start of the binary unit time interval if th...

Page 8: ... pulse after line equalisation and shaping then that pulse is not considered as a valid input to the count In any of these cases the Data Loss LED on the front panel of the module will light and the general alarm relay output will be activated connecting the general alarm output contact to ground AIS detection The data processor will detect an incoming AIS Alarm Indication Signal a series of all 1...

Page 9: ...te DA selection Handshake mode detection Two data lines are present on the handshake connector to indicate to each module that it is to operate in handshake mode Power on reset When power is applied to the pair the power on reset signal will attempt to reset both modules However as only one module can be Main the logic processor checks for handshake operation and if detected then the module which ...

Page 10: ...round indicates a loss of input or AIS detection 3 External changeover request connection to ground will make this module Main in handshake mode 4 Ground A third Krone type connector JP3 provides remote status of which unit is In Service Main Pin T1 Connection to ground indicates that module 1 is the In Service Main module T2 Connection to ground indicates that module 2 is the In Service Main modu...

Page 11: ...tandby on detection of an Alarm Indication Signal AIS OUT Enable switching to Standby on detection of an Alarm Indication Signal AIS Switch settings Sw1 Front panel push button Change request to switch to In Service Main when used with ZDA 3021RH rear assembly Sw2 Front panel slide switch Inhibit Allow request to switch to In Service Main by either Sw1 or loss of signal when used with ZDA 3021RH r...

Page 12: ... signal earth and chassis earth No attempt should be made to break this connection Installation in frame or chassis See details in separate manual for selected frame type Signal Connections G 703 data connections stand alone operation Connect the input and as many output connections as required Only good quality 75 Ohm connectors and cable should be used The use of 50 Ohm BNC connectors may cause ...

Page 13: ...information base associated with these devices has the following OIDs Object Identities Alarms In Service or Standby mode State of Change over enable switch State of link that allows or disallows a change to Standby Status on detection of incoming AIS State of link that allows or disallows the transmission of AIS when Input Loss is detected Receive PLL locked input signal present I R T C o m m u n...

Page 14: ...ANGE DATA LOSS INHIBIT ALLOW MON DDA 3020 DDA 3020 1 2 3 4 JP1 STM1 IN O P 1 O P 4 O P 2 O P 3 BYPASS 1 PWR FAIL 2 GEN ALARM 3 CHANGE REQ 4 GND SK 4 SK 3 SK 7 SK 6 SK 2 ZDA 3021RH T4 T3 T2 T1 JP1 O P 1 O P 2 O P 3 JP3 RL1 JP2 1 PWR FAIL 2 GEN ALARM 3 CHANGE REQ 4 GND T1 R TALLY T2 L TALLY T3 N C T4 GND O P 4 O P 5 4 3 2 1 4 3 2 1 RL2 I P 2 I P 1 SK 8 SK 5 SK 6 SK 7 SK 9 SK 3 SK 4 I R T C o m m u n...

Page 15: ...e with SNMP The agent therefore acts as an interface between the NMS and the managed devices The NMS sends a request message and control commands for the managed devices to the agent which in turn sends a response message containing information about the managed devices back to the NMS A managed device contains an SNMP agent and resides on a managed network Managed devices collect and store manage...

Page 16: ...rogram relevant to the module that it is plugged into Depending on the module besides the module identification parameters such as alarm states inputs and controls etc are communicated to the CDM 4000 agent via a data bus on the rear of the frame Thus the CDM 4000 collects information on what is loaded within the frame what positions they occupy and their current status for communication to the NM...

Page 17: ...ainable from the component supplier Equipment return Before arranging service ensure that the fault is in the unit to be serviced and not in associated equipment If possible confirm this by substitution Before returning equipment contact should be made with IRT or your local agent to determine whether the equipment can be serviced in the field or should be returned for repair The equipment should ...

Reviews: