Series ETSV - Models 40, 80

September 14, 2020

Page 14

• 

Refer to the National Fuel Gas Code, ANSI Z223�1 (NFPA 54) in the USA and CSA B149�1 Installation Codes in Canada, 
as well as all local requirements for general venting guidance�

• 

Series ETSV Heaters may be installed vented or unvented�

• 

Series ETSV Heaters may be vented horizontally or vertically� This series of heaters are considered a Category I appliance 
for vertical venting and a Category III appliance for horizontal venting�

• 

If heater is to be vented horizontally, the vent from building must:

* Be not less than seven feet above grade when located adjacent to public walkways�
* Terminate at least three feet above any forced air inlet located within ten feet�
* Terminate at least four feet below, four feet horizontally from or one foot above any door, window, or gravity inlet into      
   any building�
* Be located at least 12” (30cm) from any opening through which vent gases could enter a building�
* Extend beyond any combustible overhang�
* Be installed at a height sufficient to prevent blockage by snow�

• 

Secure all joints with three sheet metal screws�

• 

Optional outside air supply may be directed to the heater horizontally or vertically�

General Requirements

Venting

IMPORTANT

• 

Maximum total vent length allowed for any model heater is 15’ (3m)�

• 

Maximum total fresh air inlet duct length allowed for any model heater is 15’ (3m)�

• 

Total of vent length plus outside air supply duct length cannot exceed 30’ (6m) for any heater�

• 

If condensation in the vent pipe or outside air supply duct is a problem, shorten or adequately insulate the section�

Note:

 The above stated requirements assume a maximum of 2 elbows in the total combination of vent and air supply 

duct� Subtract 5’ of allowable length for each elbow if 3 or more elbows are used�

Un-vented Operation

• 

Requirements for combustion air supply and dilution air vary by jurisdiction, building type and specific installation details� See 
local codes for guidance� In general, fresh air ventilation must be provided to the building space at 3 cfm per 1000 BTU/Hr 
in Canada and 4 cfm per 1000 BTU/h in USA� The exhaust fan must be electrically interlocked with the heater�

• 

Optional outside air supply is not recommended for unvented heaters due to possible pressure imbalances in the building 
space�

• 

Ensure that minimum combustible clearances are maintained for unvented heaters� Refer to Clearance to Combustibles, for 
required clearance dimensions�

Summary of Contents for ETSV Series

Page 1: ...Series ETSV Models 40 80 September 14 2020 Page 1 SERIES ETSV SUBMITTAL DOCUMENT MODELS ETSV40 ETSV80...

Page 2: ...Install 8 Dimensions 8 Heater Mounting Bracket Specifications 9 Electrical Wiring 11 Internal Wiring ETSV40 80 11 Multiple Heaters Wiring Thermostat 12 Timer Specifications 13 Venting 14 Install 17 E...

Page 3: ...__________________________ STATE PROV ________________________ POSTAL CODE ZIP _____________ COUNTRY __________________ ENGINEER _____________________________________________________ ENGINEER FIRM ___...

Page 4: ...DUCT DETAILS PRODUCT BRACKET OPTIONS MODEL EXTERIOR FINISH LENGTH CEILING BRACKET KIT HORIZONTAL MOUNT WT lbs CEILING BRACKET KIT 30 ANGLE MOUNT WT lbs WALL BRACKET KIT 30 ANGLE MOUNT WT lbs ETSV40 30...

Page 5: ...information and assistance please contact us at info irenergy ca or 1 855 295 3922 Combustible Wall Mounting Bracket kits SRP has developed combustible wall mounting bracket kits for the model ETSV T...

Page 6: ...nts LOWEST PROFILE IN THE INDUSTRY Heater dimensions at 6 85 height VERSATILE Optional brackets to fit all ceiling heights wall situations TRUE TWO STAGE TECHNOLOGY Air modulated on high fire and low...

Page 7: ...let Pressure Natural Gas Maximum 14 0 W C Minimum 5 0 W C Inlet Pressure Propane Maximum 14 0 W C Minimum 11 5 W C Manifold Pressure Natural Gas High Rate 3 3 W C Low Rate 1 5 W C Manifold Pressure Pr...

Page 8: ...Series ETSV Models 40 80 September 14 2020 Page 8 Note All dimensions are in inches Model ETSV40 Model ETSV80 Dimensions TECHNICAL SPECIFICATIONS Pre Install...

Page 9: ...nsion in the case of rigid mounting the burner hanger must be free and the rest of the hangers must be fixed as outlined below Note Minimum mounting height is 7 in Canada and 8 in the US It is crucial...

Page 10: ...t brackets are available for all ETSV models 30 Ceiling Angle Mounting All Models 30 Wall Angle Mounting All Models For further information and assistance please contact us at info irenergy ca or 1 85...

Page 11: ...70 in the US and the Canadian Electric Code CSA C22 1 in Canada and must comply with all local requirements Heaters may also be controlled with a manual line switch or timer switch in place of the th...

Page 12: ...Series ETSV Models 40 80 September 14 2020 Page 12 Multiple Heaters Wiring Thermostat...

Page 13: ...to be installed in the burner or externally Input Voltage VDC 12 24 or 48 VAC 24 48 120 or 230 50 60 Hz Repeatability 0 5 Relay Life Expectancy Mechanical 20 million operations Electrical 1 million op...

Page 14: ...r supply may be directed to the heater horizontally or vertically General Requirements Venting IMPORTANT Maximum total vent length allowed for any model heater is 15 3m Maximum total fresh air inlet d...

Page 15: ...National Fuel Gas Code ANSI Z223 1 NFPA 54 in the USA and CSA B149 1 Installation Codes in Canada to size for Category I B vent fan assisted appliances Minimum vent pipe size is 4 10cm for an individu...

Page 16: ...enting of flue gases into the burner compartment Install single wall pipe or PVC pipe and fittings with a 12 linear section of flexible duct to allow movement of the heater Do not use flexible duct th...

Page 17: ...nd properly installed NEMA4 Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment to provide a d...

Page 18: ...Series ETSV Models 40 80 September 14 2020 Page 18 Multiple Heater Wiring Switch P N EE020...

Page 19: ...Code latest editions Appliance must be electrically grounded in accordance with local codes or in their absence the National Electrical Code ANSI NFPA 70 in the USA CSA C22 1 Canadian Electrical Code...

Page 20: ...pable of being ignited and burned Such materials shall be considered combustible even though flame proofed fire retardant treated or plastered Adequate clearance to sprinkler heads must be maintained...

Page 21: ...ceilings Low profile lends itself to a sleek non obtrusive look Covered patios awning canopy pergola Wall ceiling or post mount applications ETSV80 requires additional assembly time Two people are ne...

Page 22: ...ETSV SUBMITTAL DOCUMENT MODELS ETSV40 ETSV80 CANADA 563 Barton St Stoney Creek ON L8E 5S1 T 905 664 9082 TF 855 295 3922 info irenergy ca www irenergy ca USA 315 N Madison St Fortville IN 46040 T 905...

Reviews: