When option RINGON is used preconfigured number (by ALARM command) is
called within 30 seconds. No new alert is generated within 60 seconds after
alarm was detected. This option is ideal for PIR sensors which cause change of
logical 0 to logical 1 value. On the other way - it is not suitable for door sensors
which stay in switched logical 1 value. In this case alarm event is repeated until
ALARMOFF command is sent.
9.4 Alarm logs
This command helps to watch over alarm history. Device keep last 5 events in
internal memory sorted by time.
Command
Description
Response
Type
SHOWALARM
Used to list alarm history log
yy/mm/dd:hh:ss
Ctrl
This feature can be also used for example to monitor people activity in room.
In case of active ALARMON you can also switch to ALARMOFF by manual button
on device. After this manual command you can use manual button under
normal operation (not switching back to ALARMON).
More detectors can be used in parallel using by Jack splitter. Detectors
are not recognized individually, max. current generated by detectors is 50mA.
9.5 External detectors – scheme
GND
Alarm
+12V/50mA
Splitter
Connectors are not supplied with product
9.6 Microrelay – scheme
10. Date and time
Date and time are used for alarm logs and scheduling. It can be configured
manually or automatically by each incoming SMS.