30
5 - CONDENSATE DISPOSAL
To re-locate the factory-fitted trap outside the
boiler casing, use the following procedure:
Note: This procedure must be carried out before
the boiler is installed.
1 Remove the top casing panel(s) from the boiler.
2 Unscrew and remove the screws fastening the left
side panel to the rear casing panel of the boiler.
3 Carefully separate the left side and rear panels
just enough to gain access to the condensate
outlet on the left rear of the condensing heat
exchanger (see Fig.16).
4 Push out pre-cut 'knock-out' from the condensate
outlet hole in the rear of left side casing panel.
5 Remove the right angle end of the flexible
condensate discharge hose from the outlet
connection on the condensing heat exchanger.
6 From the front of boiler, remove the straight
connector end of the flexible hose from the
top of the condensate trap.
7 Reverse the flexible hose and pass the
straight connector end through the new hole
in the left hand casing panel. Push the straight
connector firmly onto the condensate outlet
connection of the condensing heat exchanger
- push on at least 20 mm.
8 Refit the left hand casing panel to the rear panel
using the reverse procedure, ensuring all fixing
screws are used.
9 Remove the trap from the mounting bracket.
10 Unscrew and remove the trap mounting bracket
from the left side panel.
11 Fix the trap mounting bracket to the wall adjacent
to the boiler in the required position.
Note: The top of the trap must be below the
condensate connection on the boiler.
12 Re-fit the trap to the mounting bracket.
The mounting bracket supplied with the trap
MUST be used - the trap should NOT be
supported by the condensate pipework only.
13 Connect the flexible condensate hose to the trap,
pushing the right angle hose connector onto
the trap inlet connection.
IMPORTANT: The flexible hose must fall continuously
from the outlet to the top of the trap.
Fig. 16 - Remove the condensate trap
Rear panel
Left hand side panel
iQE Horizon Internal Oil Boiler
iQE Horizon Internal Oil Boiler
5.7
External condensate trap fitting