IPS home inverter manual
www.ips-ups.eu
4.09.2017
IPS-home-inverter-manual_ENG-R1
4
2 Product Overview
2.1 Specifications
MODEL
300W
600W
1000W
1600W
2500W
3500W
DC Input
(the inverter must be connected to batteries to work properly
)
Nominal input voltage
12V
24V
DC input range
10 ~ 15V
20 ~ 30V
AC Input
Bypass input range
0 ~ 264Vac for 220Vac/230Vac/240Vac,
Mains input range
150 ~ 282Vac for 220Vac; 156 ~ 294Vac for 230Vac;
163 ~ 307Vac for 240Vac;
Input frequency range
50Hz / 60Hz (Auto-sense& Settable:5%
~15%,default 15%),
42.5 ~ 57.5Hz for 50Hz, 51 ~ 69Hz for 60Hz
Input range of the
generator
99 ~ 282Vac for 220Vac; 104 ~ 294Vac for 230Vac;
108 ~ 307Vac for 240Vac;
No AVR in generator mode
Input frequency range
of the generator
40 ~ 70Hz
Input power matching
of the generator
Rated power 10% ~ 150%,
regulating step 10%
,
default 120%
Output
Inverter output range
22
0Vac / 230Vac / 240Vac ± 5% or
Bypass output range
0 ~ 264Vac for 220V/230V/240V,
Mains output range
174 ~ 242Vac for 220Vac; 182 ~ 253Vac for 230Vac;
190 ~ 264Vac for 240Vac;
Output frequency
50Hz / 60Hz ± 0.3 (Auto-sense & settable)
Output waveform
Pure sine wave
Output power
300W
600W
1000W
1600W
2500W
3500W
Putput sockets
2x schuko
CEE 7/3
Block terminal
Efficiency
Max. 95% (Mains mode); Max. 80% (Inverter mode)
ECO mode
Settable, load<3%,enter in 80 s
No-load shutdown
Settable, time can be set (1 ~ 99 min), load can be set (3% ~ 50%)
Transfer time
≤ 10 ms
≤ 15 ms
Power factor
1.0
THDV
< 5% (linear load)
Inductive load
Yes
Motor load
Yes
Rectifier load
Yes
Overload capability
Mains mode: 110% 120 s; 125% 60 s; 150% 10 s (switch to bypass)
Inverter mode: 110% 60s; 125% 10 s; 150% 10s (shut down)
Battery
String battery q-ty
1
1
1
2
2
2
Charging current
(selectable)
Default
10A
Default 20A,
regulating step 1A (< 10A) / 5A (> 10A)
Max. 15A
Max. 30A Max. 40A Max. 40A Max. 50A Max. 60A
Equalizing charge
voltage
Single battery 14.4Vdc (default), 13.6 ~ 15Vdc settable
Floating charge
voltage
Single battery 13.7Vdc (default), 13.2 ~ 14.6Vdc settable
DOD
Single battery 10.8Vdc (default), 9.6 ~ 13Vdc settable
EOD
Single battery 10.2Vdc (default), 9.6 ~ 11.5Vdc settable
Reverse warning
Buzzer
Alarm
Switch on / off
Continuous beep 2 s
Low battery
Beep 0.2 s at interval of 0.4 s
Overload
Beep 2 s at interval of 2.5 s
Mains power
abnormal
Beep 0.3 s at interval of 5 s
MPPT Modules (for
–DC series only)
Model
40A
/
/