IPS IPS1000-SIN User Manual Download Page 4

 

IPS home inverter manual

 

 

 

www.ips-ups.eu                                                                                             

      

 

4.09.2017 

[email protected] 

 

 

 

 

                     IPS-home-inverter-manual_ENG-R1 

 

2 Product Overview 

2.1 Specifications 

MODEL 

300W 

600W 

1000W 

1600W 

2500W 

3500W 

DC Input 

 (the inverter must be connected to batteries to work properly

)

 

Nominal input voltage 

12V 

24V 

DC input range 

10 ~ 15V 

20 ~ 30V 

AC Input 

Bypass input range 

0 ~ 264Vac for 220Vac/230Vac/240Vac,  

Mains input range 

   150 ~ 282Vac for 220Vac;    156 ~ 294Vac for 230Vac; 
   163 ~ 307Vac for 240Vac;    

 

Input frequency range 

50Hz / 60Hz (Auto-sense& Settable:5%

 ~15%,default 15%), 

42.5 ~ 57.5Hz for 50Hz, 51 ~ 69Hz for 60Hz 

Input range of the 
generator 

   99 ~ 282Vac for 220Vac;     104 ~ 294Vac for 230Vac; 
   108 ~ 307Vac for 240Vac;    
No AVR in generator mode 

Input frequency range 
of  the generator 

40 ~ 70Hz 

Input power matching 
of the generator 

Rated power 10% ~ 150%, 

regulating step 10%

default 120% 

Output 

Inverter output range 

22

0Vac / 230Vac / 240Vac ± 5% or  

Bypass output range 

0 ~ 264Vac for 220V/230V/240V, 

Mains output range 

   174 ~ 242Vac for 220Vac;  182 ~ 253Vac for 230Vac;  
   190 ~ 264Vac for 240Vac;    

Output frequency 

50Hz / 60Hz ± 0.3 (Auto-sense & settable) 

Output waveform 

Pure sine wave 

Output power 

300W 

600W 

1000W 

1600W 

2500W 

3500W 

Putput sockets 

2x schuko 

CEE 7/3 

 

Block terminal 

Efficiency 

Max. 95% (Mains mode); Max. 80% (Inverter mode) 

ECO mode 

Settable, load<3%,enter in 80 s 

No-load shutdown 

Settable, time can be set (1 ~ 99 min), load can be set (3% ~ 50%) 

Transfer time 

≤ 10 ms 

≤ 15 ms 

Power factor 

1.0 

THDV 

< 5% (linear load) 

Inductive load 

Yes 

Motor load 

Yes 

Rectifier load 

Yes 

Overload capability 

Mains mode: 110% 120 s; 125% 60 s; 150% 10 s (switch to bypass) 

Inverter mode: 110% 60s; 125% 10 s; 150% 10s (shut down) 

Battery 

String battery q-ty 

Charging current  
(selectable) 

Default 

10A 

Default 20A, 

regulating step 1A (< 10A) / 5A (> 10A) 

Max. 15A 

Max. 30A  Max. 40A  Max. 40A  Max. 50A  Max. 60A 

Equalizing charge 
voltage 

Single battery 14.4Vdc (default), 13.6 ~ 15Vdc settable 

Floating charge 
voltage 

Single battery 13.7Vdc (default), 13.2 ~ 14.6Vdc settable 

DOD 

Single battery 10.8Vdc (default), 9.6 ~ 13Vdc settable 

EOD 

Single battery 10.2Vdc (default), 9.6 ~ 11.5Vdc settable 

Reverse warning 

Buzzer 

Alarm 

Switch on / off 

Continuous beep 2 s   

Low battery 

Beep 0.2 s at interval of 0.4 s 

Overload 

Beep 2 s at interval of 2.5 s 

Mains power 
abnormal 

Beep 0.3 s at interval of 5 s 

MPPT Modules (for 

–DC series only) 

Model 

 40A 

Summary of Contents for IPS1000-SIN

Page 1: ...ps eu IPS home inverter manual_ENG R1 1 USER MANUAL IPS home inverters with UPS function Suitable for UPS IPS300 SIN IPS300 SIN WM IPS300 SIN DC IPS600 SIN IPS600 SIN WM IPS600 SIN DC IPS1000 SIN IPS1000 SIN DC IPS1600 SIN IPS1600 SIN DC IPS2500 SIN IPS3500 SIN ...

Page 2: ...ntents 1 Safety Information 1 2 Product Overview 4 2 1 Specifications 4 2 2 Front panel features 6 2 3 Rear panel features 6 3 Installation Instructions 8 3 1 Unpacking Inspection 8 3 2 Installation 8 4 Operations 10 4 1 Turn the inverter On Off 10 4 2 Display interface 10 4 3 Settings 10 4 4 Troubleshooting 13 ...

Page 3: ... equipment which is directly related to patients life Elevator and other equipment which may endanger personal safety Safety and General Information Read all safety information and operating instructions carefully before attempting to install operate service or maintain the inverter Do not disassemble this inverter Contact your local service center if maintenance or repair is needed Disconnect all...

Page 4: ...Hz 0 3 Auto sense settable Output waveform Pure sine wave Output power 300W 600W 1000W 1600W 2500W 3500W Putput sockets 2x schuko CEE 7 3 Block terminal Efficiency Max 95 Mains mode Max 80 Inverter mode ECO mode Settable load 3 enter in 80 s No load shutdown Settable time can be set 1 99 min load can be set 3 50 Transfer time 10 ms 15 ms Power factor 1 0 THDV 5 linear load Inductive load Yes Motor...

Page 5: ... humidity Relative humidity 93 Altitude 1000m above 1000m derating 1 for each additional 100 m 4000 m max Net weight kg 8 0 8 5 7 4 10 9 11 4 11 14 0 14 6 18 0 18 5 32 0 36 0 Gross weight kg 9 0 9 5 8 4 11 9 12 4 12 15 0 15 6 19 0 19 5 34 0 38 0 Dimensions W D H mm 280 258 120 w o option 293 280 160 w option 400 210 127 Wall mounted 293 280 160 302 479 209 Packaged dimensions W D H mm 330 352 200 ...

Page 6: ...ront panel features 300W 1600W front panel 300W 600W front panel Tower type Wall mounted type 2500W 3500W front panel 2 3 Rear panel features 300W 1600W rear panel AC input socket Output sockets Overcurrent protector Buzzer for battery reverse Battery wiring Battery breaker Fan Tower type Wall mounted type ...

Page 7: ... eu IPS home inverter manual_ENG R1 7 DC output fuse MPPT optional DC output optional Optional model with MPPT DC modules 2500W 3500W rear panel Input output terminal block Overcurrent protector Battery breaker Buzzer for battery reverse Battery wring terminal Fan ...

Page 8: ...Place batteries in sound ventilation environment Use insulated tools to reduce the risk of short circuit when installing or working with the inverter the batteries or other equipments attached to this unit Be sure that the ground terminal has been connected with the ground 3 2 1 Installation information Inspect whether the battery voltage and Mains voltage are correct or not Connect the inverter w...

Page 9: ...al black cable is connected to the negative terminal 1600W inverter battery connection Optional model with MPPT modules Note that the red cable is connected to the positive terminal black cable is connected to the negative terminal 2500W 3500W inverter battery connection Note that the red cable is connected to the positive terminal black cable is connected to the negative terminal and 2500W batter...

Page 10: ...pass mode press and hold ON button for 3 seconds release it until the buzzer beeps the inverter goes to AC mode 4 2 Display interface Inverter mode Mains power mode 4 3 Settings 4 3 1 Setting operation In normal mode press and hold ON OFF button at the same time for 3 seconds to go to Setup mode In Setup mode press and hold ON OFF button at the same time for 3 seconds to exit from Setup mode and t...

Page 11: ...tion 230V 220V 230V 240V 2 INP Input power matching of the generator option 120 10 120 based on rated power 3 HZ Rated output frequency of the inverter option 50HZ 50HZ 60HZ 4 RANG Input frequency range setting option 5 5 15 5 B Equalizing charge voltage option 14 1V 13 6V 15 0V 6 F Floating charge voltage option 13 5V 13 2V 14 6V 7 A Battery low voltage alarm point setting option 10 8V 9 6V 13 0V...

Page 12: ...min 14 ACAU AC self starting function option Y Y N 15 DCAU DC auto restart function Note If select Y check whether the configured time in DC auto restart time is correct or not if not change it option N Y N 16 T DC auto restart time option 1H 0 5H 8 0H 17 ITR Input voltage display setting displays the current rated voltage of the system If select 100 240 the input voltage displays 100V 240V the tr...

Page 13: ... or supplier from whom it was purchased 4 Output overload Check the load 5 Relay fault Contact the dealer or supplier from whom it was purchased 6 MOSFET over current Contact the dealer or supplier from whom it was purchased 7 MOS overtemperature Decrease the operating load Contact the dealer or supplier if the problem persists 8 Connection of heat sink and temperature sensor abnormal Contact the ...

Page 14: ...tery voltage Contact the dealer or supplier if the problem persists 14 Charging over current Contact the dealer or supplier from whom it was purchased 15 Battery voltage is too high Check the battery voltage 16 Battery over discharge protection Check the battery voltage 17 Fault self locking Wait for auto clearance or manually shut down and restart the inverter 18 CT fault Check the CT signal line...