In normal mode and starting state, press
“OFF” button to mute.
If there is failure and failure is solved, press
“OFF” button first and release it to press “ON” button, and restart the inverter for
normal use.
4.3.2 General settings
Configure these settings at any time, using the display interface.
No.
Parameters
Default
Value
Options
LCD display
1
OUT: Rated output voltage of the
inverter (option)
230V
220V / 230V
/ 240V
2
INP: Input power matching of the
generator (option)
120%
10% ~ 120%
(based on
rated power)
3
HZ: Rated output frequency of the
inverter (option)
50HZ
50HZ / 60HZ
4
RANG: Input frequency range
setting
(option)
± 5%
± 5% ~ ±
15%
5
B: Equalizing charge voltage
(option)
14.1V
13.6V ~
15.0V
6
F: Floating charge voltage (option)
13.5V
13.2V~14.6V
7
A: Battery low voltage alarm point
setting (option)
10.8V
9.6V ~ 13.0V
8
E: End of discharge voltage
(option)
10.2V
9.6V ~ 11.5V
9
CUR: Charging current (option)
10A
(300W )
20A
(600W
~3500W)
0 ~ 60A
10
IECO: Inverter no-load ECO mode
Note: If select
“Y”, check whether the
configured load rate in
“ Inverter
shutdown load rate
” is correct or not,
if not, change it. (option)
N
Y / N