7
10kVA/8kW
50A max.
220VAC
45A
290 x 600 x 642
36
15kVA/12kW
75A max.
220VAC
68A
300 x 600 x 742
42
20kVA/16kW
100A max.
220VAC
91A
300 x 600 x 742
42
�
�
�
�
Electric
Electric
Electric
Electrical
al
al
al performance
performance
performance
performance
Input
Model
Voltage
Frequency
Power Factor
Single phase
5K
Single-phase
40Hz-70Hz
>0.98 (Full load)
Single phase
6K/10K
Single-phase
40Hz-70Hz
>0.98 (Full load)
Three-phase
10KL/15KL/ 20KL
Three-phase
40Hz-70Hz
>0.95 (full load)
Output
Voltage
regulation
Power
factor
Frequency tolerance
Distortion
Overload capacity
Current
crest ratio
±
1%
0.8lag
Synchronized 46~54Hz
in Line mode(AC mode)
±
0.1% of normal
frequency in Battery
mode.
THD<3%
Full load
(linear
load)
105%
~
125% load
transfers to bypass
mode
after
60s,125%
~
150%
load transfers to
bypass after 30s.
3:1
maximum
�
�
�
�
Operating
Operating
Operating
Operating environment
environment
environment
environment
Temperature
Humidity
Altitude
Storage temperature
0
℃
~40
℃
20%~90%
<1000m
-15
℃
~40
℃
Note: if the UPS is installed or used in a place where the altitude is above than
1000m
1000m
1000m
1000m
,
the output power must be derated in use, please refer to the following :
Altitude
(
M
)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating power
100%
95%
91%
86%
82%
78%
74%
70%
67%