Section III
Operation
Page 3.23
BP
II S, 3.00
08/96
Manual Transfer to Bypass
12. Perform this step only if
Bypass/Shutdown was skipped at Step 2.
Press
and
to obtain this screen.
13. Press
to obtain this screen.
14. Press
to manually transfer input to
bypass power source. This will inhibit
transfer and activate a red LED. It will
also change the “Inv Running” on the
screen to “Wait Rexfr.”
15. If it desired to manually retransfer to
primary UPS input, press
and wait 10
seconds for this screen to appear. This
will turn the LED to green.
16. Normally, the system will be left so that
transfer and retransfer are enabled.
Following Step 11 of this subsection,
press
once or twice to obtain this
screen with either “transfers” or
“retransfers” on the top line. Pressing
or
will change between “enabled” and
“disabled” on the bottom line.
17. Press
to obtain–
18. Press
to return to the SBS
Maintenance Menu.
0.
3.6.3.4
System Maintenance Menu
1. Press
to advance to the System
Maintenance Menu.
Man Transfer/Retransfer
Inv Running
Confirm
Yes=UP No=DN
Man Transfer/Retransfer
Inv Running
Man Transfer/Retransfer
Inv Running
Retransfers
Enabled
Return to
Previous Menu
SBS
Maintenance Menu
SBS
Maintenance Menu